4.1.17 Parameter 27 – Limit Power Factor for Compensation by Choke<br />
This parameter specifies power factor value at which the controller starts using, besides capacitive<br />
sections, inductive compensation sections for compensation as well – chokes (if available).<br />
If the power factor measured is more inductive (current more lagging) than the value specified in this<br />
parameter, the controller uses only capacitive sections (capacitors) to control compensation.<br />
If the power factor in the power system changes so that it is more capacitive (current more leading)<br />
than the limit value for compensation by choke, the controller starts using combination of capacitive<br />
and inductive compensation sections for compensation.<br />
By default this parameter’s value is set as undefined (. displayed) in a shipped controller or after<br />
its initialization. With this setting the controller does not use chokes that are available (such sections<br />
are permanently disconnected) and it does not even detect available chokes in the automatic section<br />
power recognition process.<br />
Compensation by chokes is described in more detail in an appropriate chapter further below.<br />
4.1.18 Parameter 30 – Alarm Setting<br />
<strong>NOVAR</strong> line controllers feature two alarm type functions that are independent of each other:<br />
alarm indication<br />
alarm actuation<br />
4.1.18.1 Alarm Indication<br />
In order to indicate nonstandard compensation conditions, the instruments feature an Alarm LED in<br />
the front panel and an Alarm relay potential-free contact accessible at a connector in the rear panel. At<br />
<strong>NOVAR</strong> 10xx models, that are not equipped with the dedicated Alarm relay, it is possible to use any of<br />
highest two outputs for Alarm signalling ( see parameter 26).<br />
Indication of a nonstandard condition occurrence shows as flashing Alarm LED and closed Alarm<br />
relay contact. In standard condition this LED is dark and the relay contact open. At <strong>NOVAR</strong> 10xx<br />
models, the relay state polarity is presetable, but it is always opened if voltage outage.<br />
Nonstandard condition, at which alarm should be indicated, can be specified in the side branch of<br />
parameter 30. Any of the eight conditions shown in Table 4.5 can trigger the alarm indication.<br />
Alarm indication from any nonstandard condition can be selected by editing such a condition in the<br />
side branch of parameter 30. The settings can take 4 different values:<br />
1. ... condition 1 (undercurrent) is not indicated (neither does it trigger actuation – see<br />
description further below)<br />
2. ... condition 1 (undercurrent) is indicated (but it does not trigger actuation)<br />
3. ... condition 1 (undercurrent) is not indicated (but it triggers actuation)<br />
4. ... condition 1 (undercurrent) is indicated (and it triggers actuation)<br />
Alarm indication can be set for any other condition in the same manner as shown for condition 1 in the<br />
above example. For some conditions, alarm actuation can be specified besides indication (see<br />
description further below).<br />
Alarm indication can be triggered by one or a combination of some conditions specified. Alarm<br />
indication will be triggered when the condition has been detected continuously for the time specified in<br />
Table 4.5 as the 1 st value; the 2 nd value (after „/―) defines elapse time to stop alarm indication after the<br />
condition disappears. The condition that has triggered alarm indication can then be checked in the<br />
alarm status (in the side branch of parameter 40).<br />