<strong>NOVAR</strong> <strong>1xxx</strong> EPM Elektropřístroj s. r. o.<br />

or identified (in the automatic section power recognition process). Under this condition, flashing<br />

is shown on the numeric display.<br />

4.1.18.2 Alarm Actuation<br />

Independently of the alarm indication function, you can set alarm actuation for some of the<br />

nonstandard conditions. Actuation means intervention in the control process, especially interruption of<br />

controller operation, usually with subsequent disconnection of compensation sections. See list of<br />

actuations in Table 4.6.<br />

If you require that the controller respond to occurrence of an above nonstandard condition with its<br />

corresponding actuation as shown in the table, you have to set the condition of choice in the side<br />

branch of parameter 30 toor(see previous chapter).<br />

Conditions not shown in this table do not trigger any actuations, hence they can not be set this way<br />

either.<br />

Table 4.6: Alarm – actuation<br />

# condition minimum delay of<br />

actuation<br />

activation / deactivation<br />

1 undercurrent 10 / 5 seconds disconnection of all sections<br />

except fixed ones<br />

3 voltage failure immediately / 5 seconds disconnection of all sections<br />

4 undervoltage maximum 1 minute (depends disconnection of all sections<br />

on the extent of<br />

undervoltage)<br />

5 overvoltage maximum 1 minute (depends disconnection of all sections<br />

on the extent of overvoltage)<br />

6 THDI > maximum 1 minute (depends disconnection of all sections<br />

on the level of THDI)<br />

7 THDU > maximum 1 minute (depends disconnection of all sections<br />

on the level of THDU)<br />

8 CHL > maximum 1 minute (depends disconnection of all sections<br />

on the level of CHL)<br />

10 power export maximum 1 minute (depends<br />

on the level of active power)<br />

disconnection of all sections<br />

except fixed ones<br />

12 section error 5 connections +<br />

5 disconnections<br />

section disablement (see<br />

description in chapter below)<br />

13 overheated maximum 1 minute (depends disconnection of all sections<br />

on the level of temperature)<br />

14 external alarm immediately / 5 seconds disconnection of all sections<br />

Note: Conditions shown above in bold type are set by default.<br />

4.1.19 Parameters 31 through 37 – Alarm Indication/Actuation Limits<br />

If indication or actuation from a condition shown in Table 4.7 is set up, you also need to specify the<br />

relevant quantity’s limit value exceeding which triggers the indication or actuation. The table shows<br />

parameter numbers where the limits are stored, limit setup ranges, and limit default values.<br />

38