<strong>NOVAR</strong> <strong>1xxx</strong> EPM Elektropřístroj s. r. o.<br />
or identified (in the automatic section power recognition process). Under this condition, flashing<br />
is shown on the numeric display.<br />
4.1.18.2 Alarm Actuation<br />
Independently of the alarm indication function, you can set alarm actuation for some of the<br />
nonstandard conditions. Actuation means intervention in the control process, especially interruption of<br />
controller operation, usually with subsequent disconnection of compensation sections. See list of<br />
actuations in Table 4.6.<br />
If you require that the controller respond to occurrence of an above nonstandard condition with its<br />
corresponding actuation as shown in the table, you have to set the condition of choice in the side<br />
branch of parameter 30 toor(see previous chapter).<br />
Conditions not shown in this table do not trigger any actuations, hence they can not be set this way<br />
either.<br />
Table 4.6: Alarm – actuation<br />
# condition minimum delay of<br />
actuation<br />
activation / deactivation<br />
1 undercurrent 10 / 5 seconds disconnection of all sections<br />
except fixed ones<br />
3 voltage failure immediately / 5 seconds disconnection of all sections<br />
4 undervoltage maximum 1 minute (depends disconnection of all sections<br />
on the extent of<br />
undervoltage)<br />
5 overvoltage maximum 1 minute (depends disconnection of all sections<br />
on the extent of overvoltage)<br />
6 THDI > maximum 1 minute (depends disconnection of all sections<br />
on the level of THDI)<br />
7 THDU > maximum 1 minute (depends disconnection of all sections<br />
on the level of THDU)<br />
8 CHL > maximum 1 minute (depends disconnection of all sections<br />
on the level of CHL)<br />
10 power export maximum 1 minute (depends<br />
on the level of active power)<br />
disconnection of all sections<br />
except fixed ones<br />
12 section error 5 connections +<br />
5 disconnections<br />
section disablement (see<br />
description in chapter below)<br />
13 overheated maximum 1 minute (depends disconnection of all sections<br />
on the level of temperature)<br />
14 external alarm immediately / 5 seconds disconnection of all sections<br />
Note: Conditions shown above in bold type are set by default.<br />
4.1.19 Parameters 31 through 37 – Alarm Indication/Actuation Limits<br />
If indication or actuation from a condition shown in Table 4.7 is set up, you also need to specify the<br />
relevant quantity’s limit value exceeding which triggers the indication or actuation. The table shows<br />
parameter numbers where the limits are stored, limit setup ranges, and limit default values.<br />
38