<strong>NOVAR</strong> <strong>1xxx</strong> EPM Elektropřístroj s. r. o.<br />
Notes:<br />
<br />
phase measurement voltage -<br />
<br />
line measurement voltage - <br />
# connection # connection<br />
1 1 <br />
2 2 <br />
3 3 <br />
4 4 <br />
5 5 <br />
6 6 <br />
It is assumed that the metering current transformer is in phase 1 and its orientation (terminals<br />
k, l) corresponds to real orientation supply –> appliance.<br />
<br />
The method of connection is shown as x–y where x represents the phase connected to<br />
controller’s terminal L and y represents the phase connected to controller’s terminal N/L (0<br />
represents the neutral wire).<br />
If the method of connection value is entered as not specified (---- value), the automatic connection<br />
configuration detection process is started, with exception of case when linear switching mode ( see<br />
parameter 21) is set. In such case the process is not started and it is necessary to set the method of<br />
connection manually.<br />
If the type of connection (phase or line, parameter 15) is changed, the method of connection<br />
(parameter 16) is automatically set to the unspecified value.<br />
4.1.9.1 Setting Type of Connection Configuration if Measuring at Power Supply<br />
Transformer’s Opposite Sides<br />
If the measurement current signal is from the power supply transformer’s side which is opposite to<br />
measurement voltage signal side, the transformer phase angle is conclusive for correct parameter 15<br />
setting. This value specifies the angle between voltage vectors of corresponding phases at primary<br />
and secondary sides. The transformer phase angle can be in the range from 0 to 11, corresponding to<br />
phase angles from 0 to 330 degrees (in steps of thirty degrees).<br />
Provided the measurement voltage signal is connected in accordance with the type of transformer<br />
(that is phase measurement voltage is connected to controller with wye, or star, connection or line<br />
measurement voltage with delta connection), it is necessary to set phase type of connection with<br />
even transformer phase angle value and line type of connection with odd transformer phase angle<br />
value.<br />
If the measurement voltage signal is connected in disaccordance with the type of transformer, the<br />
opposite rule applies: line connection with even transformer phase angle or phase connection with<br />
odd transformer phase angle.<br />
Determining parameter 15 explained in practical examples:<br />
Example 1:<br />
Compensation is to be provided for consumption supplied via a Dy1 transformer while line<br />
measurement voltage will be taken from its primary side (D stands for delta connection) and<br />
measurement current signal from a metering current transformer at the power supply transformer’s<br />
secondary side (y stands for wye, or star, connection).<br />
30