<strong>NOVAR</strong> <strong>1xxx</strong> EPM Elektropřístroj s. r. o.<br />

Notes:<br />

<br />

phase measurement voltage -<br />

<br />

line measurement voltage - <br />

# connection # connection<br />

1 1 <br />

2 2 <br />

3 3 <br />

4 4 <br />

5 5 <br />

6 6 <br />

It is assumed that the metering current transformer is in phase 1 and its orientation (terminals<br />

k, l) corresponds to real orientation supply –> appliance.<br />

<br />

The method of connection is shown as x–y where x represents the phase connected to<br />

controller’s terminal L and y represents the phase connected to controller’s terminal N/L (0<br />

represents the neutral wire).<br />

If the method of connection value is entered as not specified (---- value), the automatic connection<br />

configuration detection process is started, with exception of case when linear switching mode ( see<br />

parameter 21) is set. In such case the process is not started and it is necessary to set the method of<br />

connection manually.<br />

If the type of connection (phase or line, parameter 15) is changed, the method of connection<br />

(parameter 16) is automatically set to the unspecified value.<br />

4.1.9.1 Setting Type of Connection Configuration if Measuring at Power Supply<br />

Transformer’s Opposite Sides<br />

If the measurement current signal is from the power supply transformer’s side which is opposite to<br />

measurement voltage signal side, the transformer phase angle is conclusive for correct parameter 15<br />

setting. This value specifies the angle between voltage vectors of corresponding phases at primary<br />

and secondary sides. The transformer phase angle can be in the range from 0 to 11, corresponding to<br />

phase angles from 0 to 330 degrees (in steps of thirty degrees).<br />

Provided the measurement voltage signal is connected in accordance with the type of transformer<br />

(that is phase measurement voltage is connected to controller with wye, or star, connection or line<br />

measurement voltage with delta connection), it is necessary to set phase type of connection with<br />

even transformer phase angle value and line type of connection with odd transformer phase angle<br />

value.<br />

If the measurement voltage signal is connected in disaccordance with the type of transformer, the<br />

opposite rule applies: line connection with even transformer phase angle or phase connection with<br />

odd transformer phase angle.<br />

Determining parameter 15 explained in practical examples:<br />

Example 1:<br />

Compensation is to be provided for consumption supplied via a Dy1 transformer while line<br />

measurement voltage will be taken from its primary side (D stands for delta connection) and<br />

measurement current signal from a metering current transformer at the power supply transformer’s<br />

secondary side (y stands for wye, or star, connection).<br />

30