Bulletin 150 SMC Flex<br />

Linear Speed Acceleration with Selectable Kickstart<br />

This method starts the motor following a linear speed ramp. The ramp time defines the time the<br />

motor will ramp from zero speed to full speed. This ramp time is user adjustable from<br />

0…30 seconds. Linear Speed requires a tachometer input (0…5 V DC, 4.5 V = 100% speed).<br />

The curent limit is active during the starting ramp.<br />

The kickstart feature provides a boost at startup to break away loads that may require a pulse of<br />

high torque to get started. It is intended to provide a current pulse, user adjustable 0…90%<br />

locked rotor torque for a selected period of time, 0.0…2.0 seconds. Note that speed ramp<br />

begins once the kickstart is completed.<br />

Figure 1.17: Linear Speed Acceleration<br />

Percent<br />

Speed<br />

100%<br />

Start<br />

Run<br />

Time (seconds)<br />

Stop<br />

The basic parameter set for Linear Speed follows:<br />

Table 1.F: Linear Speed Acceleration Parameters<br />

Parameter<br />

SMC Option<br />

Starting Mode<br />

Ramp Time<br />

Current Limit Level<br />

Kickstart Time<br />

Kickstart Level<br />

Option 2<br />

Stop Mode<br />

Stop time<br />

<strong>Stand</strong>ard<br />

Linear Speed<br />

0.0…30.0 s<br />

0…600% FLC (Full Load Current)<br />

0.0…2.0 s<br />

0…90% LRT<br />

Disable<br />

Linear Speed<br />

0.0…120.0 s<br />

Adjustments<br />

1-18