Bulletin 150 SMC Flex<br />

Multi-motor<br />

Applications<br />

The SMC-Flex controller will operate with more than one motor connected to it. To size the<br />

controller, add the total nameplate amperes of all of the connected loads. The stall and jam<br />

features should be turned off. Separate overloads are still required to meet the National Electric<br />

Code (NEC) requirements.<br />

Note:<br />

The SMC-Flex controller’s built-in overload protection cannot be used in multi-motor<br />

applications.<br />

Figure 3.4: Multi-Motor Application<br />

3-Phase<br />

Input Power<br />

L1/1<br />

L2/3<br />

L3/5<br />

T1/2<br />

T2/4<br />

T3/6<br />

Motor<br />

No. 1<br />

➀<br />

Branch<br />

Protection<br />

➀<br />

SMC-Flex<br />

Controller<br />

Overload<br />

Relay (O.L.)<br />

➀<br />

➀ Customer Supplied<br />

Motor<br />

No. 2<br />

➀<br />

Overload<br />

Relay (O.L)<br />

➀<br />

3-5