New Jersey Schools Development Authority<br />

Design-Build Performance Specifications<br />

New Caruso Elementary School<br />

Keansburg Public Schools<br />

5. Locksets: Unless specifically indicated as one type, rim exit devices.<br />

a. Do not use rim type auxiliary locks, lock combinations requiring two hands for<br />

operation, interconnected locks, or bored (cylindrical locks).<br />

6. Door closers: Unless specifically indicated as one type, surface overhead frame-mounted<br />

type or surface overhead door-mounted type.<br />

a. Unless specifically indicated, do not use concealed overhead type, floor mounted<br />

type, or spring hinges.<br />

b. Mount closer on interior/room side <strong>of</strong> door.<br />

7. Door stops: Unless specifically indicated as one type, overhead door/frame mounted<br />

type.<br />

a. Do not use floor-mounted type or wall-mounted type.<br />

8. Door hold-opens: Unless specifically indicated as one type, overhead door/frame<br />

mounted type.<br />

9. Protection: Provide mechanically fastened stainless steel push plates and/or kick<br />

plates/mop plates at locations subject to service use or use by wheeled carts.<br />

10. Silencers: Provide three silencers on each door frame.<br />

J. Do not use:<br />

1. Different metals subject to galvanic action in direct contact with each other.<br />

2. Aluminum in direct contact with concrete or cementitious materials.<br />

K. Frames<br />

1. Provide steel or aluminum frames in accordance with door material and appearance.<br />

a. Aluminum shall be a minimum <strong>of</strong> 1/8 inch (.125) thick, 6063 alloy T5 and 6061 alloy<br />

T6, for all aluminum entrance door and frame sections.<br />

2. Frame corners shall be internally reinforced and fully welded unit construction, with<br />

corners mitered and continuously welded full depth and width <strong>of</strong> frame. Frame shall be<br />

back welded.<br />

3. Entrance frames shall be mortised, reinforced, drilled and tapped for all mortise hardware<br />

per templates from the hardware supplier.<br />

4. Exterior doors and frames shall be weatherstripped at head, jambs, sills and meeting rails.<br />

Weatherstrip shall be continuous, vandal-resistant and field replaceable.<br />

5. Knock-down frames will not be accepted.<br />

6. Entrance door frames shall have continuous internal 12 gauge steel channel in hinge stile<br />

and jamb, arranged to reinforce mounting hinges.<br />

7. Provide frames at masonry openings with UL type masonry anchors, minimum <strong>of</strong> three<br />

per frame at each jamb.<br />

8. Provide caulking stops, filler pieces and trim where required, integrally formed as part <strong>of</strong><br />

the frame.<br />

9. Provide hardware reinforcement where specified by hardware manufacturer.<br />

10. Provide cutouts and reinforcing for security devices as required.<br />

June 27, 2013 Section B2050.00 Page 5 <strong>of</strong> 9<br />