10. To exit the programming mode, press .<br />

Table 3 Programmable function definitions<br />

Prg Definition of parameter Unit Lower / Default<br />

No.<br />

Upper Limit<br />

P00 Alternator Voltage Lower Limit VAC 60-600 300<br />

P01 Alternator Voltage Upper Limit VAC 60-600 440<br />

P02 Speed Lower Limit Hz. 30.0-75.0 47.0<br />

P03 Speed Upper Limit Hz. 30.0-75.0 53.0<br />

P04 Battery Voltage Lower Limit VDC 7.2-24.0 8.0<br />

P05 Reserved<br />

P06 Periodic Maintenance Hour Set Hour 0-9999 5000<br />

P07 Periodic Maintenance Reset Press DECREMENT Button For Reset<br />

P08 Horn Duration Second<br />

0 = Contin.<br />

1-999<br />

60<br />

P09 Preheat time Second 0 – 99 10<br />

P10 Single/Three Phase Selection 1/3 3<br />

P11 Nominal Alternator Frequency Hz. 50 / 60 50<br />

P12 Nominal Speed (RPM) Rpm 500-5000 3000<br />

P13 Number of Flywheel Teeth Number 1-1000 100<br />

P14 Reserved<br />

Speed Sensing Input Selection<br />

P15 0-Alternator Signal (Internal) Number 0 / 1 0<br />

1-Magnetic Pickup<br />

P16 Stop/Fuel Solenoid Selection Stop / Fuel Stop / Fuel Fuel<br />

P17 Stop Magnet Energising Time Second 0-99 20<br />

P18 Engine Started Signal 0: No, 1: Yes<br />

P18.0 Charge Generator 0/1 1<br />

P18.1 Speed 0/1 0<br />

P18.2 Alternator Voltage 0/1 1<br />

P18.3 Oil Pressure 0/1 0<br />

P19 Battery Voltage Weak Limit VDC 6.0-14.4 7.0<br />

P20 Battery Voltage Weak Control Time Second 1-99 3<br />