Section 7 Specification<br />
Inputs<br />
DC Supply<br />
<strong>Operating</strong> Current<br />
Cranking Dropout<br />
Generator Voltage<br />
Magnetic Pickup<br />
Contact Sensing<br />
12V (8 to 16V) or 24V (16 to 32V) DC, Switch Selectable<br />
350mA maximum, 12V range<br />
400mA maximum, 24V range<br />
Battery voltage can be 0V DC for max. 100 ms during<br />
cranking (battery voltage should be at least nominal<br />
voltage before cranking)<br />
35 to 300V AC L-N, 10 to 110Hz<br />
4 Wire connection for three phase, 2 wire connection for<br />
single phase.Neutral <strong>and</strong> battery negative must<br />
be grounded.<br />
3 to 35 Volts peak, 35Hz to 10kHz<br />
Emergency Stop (NC)<br />
Oil Pressure switch (NC)<br />
Temperature Switch (NO)<br />
Remote Start/Stop input (NO)<br />
Configurable input 1 (NO)<br />
Configurable input 2 (NO)<br />
Configurable input 3 (NO)<br />
Outputs<br />
Relay Contacts<br />
Start relay (12 Amp DC at 12/24V)<br />
Fuel relay (12 Amp DC at 12/24V)<br />
Horn relay (5 Amp DC at 12/24V)<br />
Configurable relay 1 (5 Amp DC at 12/24V)<br />
Configurable relay 2 (5 Amp DC at 12/24V)<br />
Charge Generator<br />
Excitation current 200mA, maximum 3 Watts.<br />
Display<br />
Display Type<br />
Displayed Parameters<br />
4 digits, 7 segment LED, high visibility<br />
Generator Voltage, Line to Neutral<br />
Generator Voltage, Line to Line<br />
Generator Frequency<br />
Engine RPM<br />
33