2 This is the same as 1 but, in addition, the engine is stopped.<br />
3 Contactor releaser. It is valid only if the load transfer permit is selected in configuration<br />
outputs 1 <strong>and</strong> 2.<br />
3.2.16 Configurable relay outputs 1-2 (P35, P36)<br />
When active, these outputs provide up to 5A at the battery voltage (12V or 24V). Each can be<br />
programmed as follows:<br />
0 Alarm output. Active when any fault is reported. Can be used for either audible or visual<br />
alert.<br />
1 Engine running. Active while the engine is running.<br />
2 Load transfer permitted. This output is active while the alternator output voltage is between<br />
the upper <strong>and</strong> lower limit defined by parameters P00 <strong>and</strong> P01. This output can be use to<br />
control a contactor that transfers the load to the alternator once the alternator set is up <strong>and</strong><br />
running.<br />
3 Preheat function. On starting the generator this output is active for time period defined in<br />
Preheat Time (P09) prior to running the starter motor.<br />
3.2.17 Maintenance Indication<br />
P06 Periodic Maintenance Hour Set Value<br />
P07 Periodic Maintenance Hour Reset<br />
To ensure reliability, the engine must be serviced at regular intervals. The unit can be set to<br />
indicate when a service is due. Set P06 to the number of running hours between services. Use<br />
P07 to reset the hours counter at each service. When the engine has run for the defined number<br />
of hours, the alarm LED will flash <strong>and</strong>, when the alarm display option is selected, the display will<br />
read the error message bAEr.<br />
3.2.18 Operator password (P37)<br />
Use this option to change the Operator password. This password allows access to program<br />
parameters P00 to P08 <strong>and</strong> P37.<br />
3.2.19 Technician Password (P38)<br />
Use this option to change the Technician password. It allows access to all the program<br />
parameters (P00 to P38).<br />
25