6.2.5 Low/High Speed LED<br />
This LED flashes if the alternator speed goes outside the values defined by the Speed Lower<br />
Limit (P02) <strong>and</strong> Speed Higher Limit (P03) parameters. For a fault to be indicated, the speed must<br />
be outside these limits for longer than the period defined by the Speed Fault Control Delay<br />
parameter P28.<br />
Alternator speed is measured either by measuring alternator output frequency or by monitoring<br />
an external magnetic pick-up, as selected by program parameter P15.<br />
This failure immediately stops the generating set, without any cool-down period.<br />
6.2.6 Alternator Voltage Failure LED<br />
This LED flashes if the alternator output fails to reach the value specified by the Alternator<br />
Voltage Lower Limit parameter P01 within the period defined by the Control On Delay<br />
parameter P26.<br />
This failure immediately stops the generating set, without any cool-down period.<br />
6.2.7 EStP– Emergency Stop<br />
The remote Emergency Stop button has been pressed <strong>and</strong> has shut down the engine. Press<br />
Reset to remove the indication <strong>and</strong> restore unit operation.<br />
6.2.8 bAT1 - Low Battery Voltage message<br />
This message appears if, while the engine is running, the battery voltage falls below the value<br />
specified by the Battery voltage lower limit parameter P04. The unit measures battery voltage at<br />
the rear terminals. Depending on the size <strong>and</strong> length of the cable to the battery, this may be<br />
somewhat less than the voltage as measured at the battery.<br />
6.2.9 bAT2 - Weak Battery Alarm message<br />
This message appears if, during engine cranking, the battery voltage drops below the value<br />
specified by the Battery Voltage Weak Limit parameter P19 for longer than the period specified<br />
by the Battery Voltage Weak Control Time parameter P20. The message is reset by Reset<br />
button.<br />