Section 1 Introduction<br />
These products provide control <strong>and</strong> protection in the operation of a generator set. The units<br />
allow starting <strong>and</strong> stopping of the engine <strong>and</strong> indicates status <strong>and</strong> fault conditions. The unit<br />
monitors:<br />
●<br />
●<br />
●<br />
●<br />
Engine temperature,<br />
Oil pressure,<br />
Charging Alternator<br />
Alternator output (voltage <strong>and</strong> frequency).<br />
It controls:<br />
●<br />
●<br />
●<br />
●<br />
●<br />
Engine fuel supply or engine stopping, via external solenoid<br />
Starter motor, via external relay.<br />
Alarm horn<br />
Preheating (configurable relay feature)<br />
Load transfer (configurable relay feature)<br />
A four-digit, seven-segment display provides extensive monitoring of unit <strong>and</strong> alternator<br />
parameters, including:<br />
●<br />
●<br />
●<br />
●<br />
●<br />
●<br />
Alternator output voltage <strong>and</strong> frequency<br />
Engine RPM<br />
Battery voltage<br />
Elapsed time<br />
Error indication<br />
Program parameters<br />
The unit is extensively programmable, with password protection on two levels.<br />
In the event that the engine fails to start on the first attempt, the attempt will be repeated a<br />
programmed number of times or until successful.<br />
If a fault is detected, the unit shuts down the engine <strong>and</strong> indicates the failure by flashing an<br />
appropriate fault LED.<br />
Remote fuel, start <strong>and</strong> emergency stop inputs provide for remote control of the engine.<br />
Three user-defined inputs are included that sound an external horn, flash indicators on the panel<br />
<strong>and</strong> can be programmed to stop the engine.<br />
Two extra outputs can be configured to act on an alarm, when the engine is running, when a<br />
load can be transferred to the alternator, or when engine preheating is required.<br />
The operational parameters of the unit can be monitored <strong>and</strong> controlled from a PC via a built-in<br />
RS-232 port.<br />
5