Maintenance Instructions<br />

Fill in cooling water into the cooling water<br />

filler neck. If it is to be recognized that the<br />

cooling water level does not fall anymore<br />

(with cold cooling water the cooling water<br />

levelmust cover the sheet metal in the<br />

exhaust elbow), close the filler-cap and<br />

the cooling water screws and start the<br />

generator.<br />

Now the cooling water is only filled over the external expansion tank. This is connected by 2<br />

hoses with the genset.<br />

The external expansion tank should be filled in the cold condition only up to maximally<br />

20%. It is very important that a large extension space over the cooling water level remains.<br />

Repeat this procedure several times.<br />

If no change of the cooling water level can be determined, the generator is started for 5 minutes.<br />

Afterwards repeat the de-aeration two - three times.<br />

It is meaningful to repeat the de-aeration procedure also after some days again to guarantee that<br />

in the system remained bubbles are removed.<br />

The de-aerating screw over the housing of<br />

the cooling water pump may be opened<br />

under no circumstances, while the generator<br />

runs. If this happens inadvertently,<br />

through the opening air is sucked in. A<br />

very complex de-aerationt of the entire<br />

system is necessary thereafter.<br />