<strong>Generator</strong> Failure<br />
Possible disturbances in the area of the rev regulation "VCS"<br />
Failure<br />
The spindle of the actuator jams<br />
Fuse on the printed circuit board of the<br />
VCS control is melted.<br />
Cause<br />
• not regularly lubricated.<br />
• surface is mechanical damaged.<br />
• actuator is defect.<br />
• defect of the VCS control (short of winding).<br />
• signal 240V (120V) AC missing.<br />
• limiting nut jams the spindle.<br />
• constant overload of the generator.<br />
Steps to check the voltage control by a disturbance:<br />
1. Switch off all electrical load.<br />
2. Disconnect the plug of the actuator.<br />
3. Turn the actuator manually to check if the adjusting nut is jamed to the limit stop points.<br />
4. Turn the actuator manually to check if the adjusting nut on the spindel runs faultless.<br />
If there is no result by these steps the actuator is working mechanically correct. After this the<br />
electrical components must be checked:<br />
1. Connect the plug of the actuator.<br />
2. Start the generator.<br />
3. Turn the actuator by hand and check if the spindle turns back by the motor.<br />
4. If the motor react on the turn by manual strongly (the motor can normally hold with the fingers)<br />
the drive will be working faultless. If there are nevertheless faults in the voltage control there is<br />
a fault in the control VCS.<br />
If the actuator is not moving the following points are necessary:<br />
1. The motor turns not strongly rather weak:<br />
• The actuator has shorts in the winding and must be changed. (pay attention that the generator<br />
is not overloaded anymore.)<br />
2. The actuator does not move but the spindle can be turned manually. Disconnect the plug of<br />
the actuator. Connect provisional an external voltage source 12V-DC to the motor.<br />
• The actuator don’t turns with the external voltage source. The actuator is defect and have to<br />
be changed.<br />
• The control must be inspected by the following steps if the actuator turns und works faultless<br />
with the external voltage source:<br />
1. Check the fuse on the VCS printed circuit board.<br />
2. Check if the sense voltage is wired to the VCS printed circuit board.<br />
3. Check if the VCS supply voltage is wired to the VCS.<br />
4. Check if the VCS outlet signal for the actuator is wired.<br />
Change the VCS printed circiut board if the points above carries no clearance.<br />
Page 36<br />