(4) Pump-Out Cycle<br />

LEDs 1, 3, and 2 are on. Comp remains energized. HGV energizes. WV energizes if<br />

S4 dip switch 3 off and 4 on (LED 4 on). LLV (<strong>KM</strong>-515MAH-E) and FM de‐energize.<br />

PM stops for 2 seconds then reverses for 10 or 20 seconds (S4 dip switch 3 & 4).<br />

Water is removed from the bottom of the water tank through the check valve and<br />

down the drain. At the same time, water flows through the small F/S tube to power<br />

flush F/S. When the pump-out timer terminates, pump-out is complete.<br />

The 1st pump‐out occurs after the 1st freeze cycle, then every 10th cycle<br />

thereafter (<strong>KM</strong>-320MAH-E) or every cycle thereafter (<strong>KM</strong>-515MAH-E and<br />

<strong>KM</strong>‐<strong>650MAH</strong>-E). The pump-out frequency control is factory set, and generally no<br />

adjustment is required. However, the pump-out frequency control (S4 dip switch 5 &<br />

6) can be set to have a pump-out occur every cycle, or every 2, 5, or 10 cycles. For<br />

details, see "II.C.3.d) Pump‐Out Frequency Control (S4 dip switch 5 & 6)."<br />

(5) Harvest Cycle<br />

LEDs 1, 4, and 2 are on. Same as the initial harvest cycle. See "II.B.1.a)(2) Initial<br />

Harvest Cycle."<br />

Note: Icemaker continues to cycle until TBC is satisfied or power is turned off. The<br />

icemaker always restarts at the 1-minute fill cycle.<br />

(6) Shutdown<br />

When ice contacts the thermostatic bulb (TBC switch open), TBC shuts down the<br />

icemaker within 10 seconds. TBC is factory set, and generally no adjustment is<br />

required. However, adjustment may be needed in some conditions, particularly at<br />

higher altitude locations. NOTICE! Do not adjust S4 dip switch 7 out of the factory<br />

default position. This dip switch must be left in the factory default position or<br />

this icemaker will not operate correctly.<br />

Legend: CB–control board; Comp–compressor; FM–fan motor; F/S–float switch; HGV–hot<br />

gas valve; LLV–liquid line valve (<strong>KM</strong>-515MAH-E); PM–pump motor;<br />

TBC–thermostatic bin control; WV–inlet water valve<br />

14