7) Normal Harvest Cycle – same as the initial harvest cycle – See "IV.A.4) Initial Harvest<br />
Cycle."<br />
8) Shutdown<br />
a) Thermostatic Bin Control:<br />
<strong>KM</strong>-320MAH-E and <strong>KM</strong>-<strong>650MAH</strong>-E Auxiliary Code U-0 and Earlier<br />
<strong>KM</strong>-515MAH-E Auxiliary Code U-1 and Earlier<br />
When the icemaker is running hold ice in contact with the thermostatic bulb,<br />
TBC switch opens within 10 seconds, shutting down the icemaker. TBC is<br />
factory set, and generally no adjustment is required. However, adjustment<br />
may be needed in some conditions, particularly at higher altitude locations.<br />
NOTICE! Do not adjust S4 dip switch 7 out of the factory default position<br />
on this model. This dip switch must be left in the factory default position<br />
or this icemaker will not operate correctly. Diagnosis: See "IV.C.1.<br />
Thermostatic Bin Control Check: Auxiliary Code U-0 and Earlier."<br />
b) Mechanical Bin Control:<br />
<strong>KM</strong>-320MAH-E and <strong>KM</strong>-<strong>650MAH</strong>-E Auxiliary Code U-1 and Later<br />
<strong>KM</strong>-515MAH-E Auxiliary Code U-2 and Later<br />
See "IV.C.2.a) Mechanical Bin Control Check."<br />
Legend: CB–control board; Comp–compressor; FM–fan motor; F/S–float switch;<br />
HGV–hot gas valve; LLV–liquid line valve (<strong>KM</strong>-515MAH-E); MBC–mechanical<br />
bin control; PM–pump motor; TBC–thermostatic bin control; TXV–thermostatic<br />
expansion valve; WV–inlet water valve<br />
38