Installation & Operation Manual - Phase-A-Matic, Inc.
Installation & Operation Manual - Phase-A-Matic, Inc.
Installation & Operation Manual - Phase-A-Matic, Inc.
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Section 3<br />
Receiving & <strong>Installation</strong><br />
Receiving & Inspection When you receive your generator, there are several things you should do immediately.<br />
1. Observe the condition of the shipping container and report any damage immediately to<br />
the commercial carrier that delivered your system.<br />
2. Verify that the part number of the system you received is the same as the part number<br />
listed on your purchase order.<br />
3. If the system is to be stored for several weeks before use, be sure that it is stored in a<br />
location that conforms to published storage temperature and humidity specifications.<br />
Lifting the Generator When lift or hoist equipment is used to lift the generator and move it to position, be careful not<br />
to contact overhead wires or other obstacles. The generator can weigh as much as 1,500 lbs. Be<br />
sure lift or hoist equipment has appropriate tires for the terrain to avoid becoming stuck or tipping<br />
over. If the shipping pallet is intact, use a fork lift to move the generator. If the shipping pallet has<br />
been removed, use two steel pipes through the “Lift Point” holes to lift the generator. See Figure 3-1.<br />
Figure 3-1 Generator Lifting & Mounting<br />
AE8 & AE10<br />
Not To Scale<br />
Length<br />
Four mounting<br />
holes 0.38" dia.<br />
8.88<br />
Electrical<br />
Stub Up<br />
2.63<br />
8.88<br />
7.75<br />
Fuel Inlet on<br />
Horizontal Surface<br />
Height<br />
44.50<br />
Lift Point<br />
Thru Base<br />
Stub Up Area<br />
Stub Up<br />
Access Panel<br />
(Fuel & Electrical)<br />
1.50<br />
Lift Point<br />
1.50<br />
4.52<br />
6.00<br />
AE11<br />
Width<br />
All dimensions are in inches.<br />
Six mounting<br />
holes 0.410" dia.<br />
24.00<br />
(Alternator End)<br />
29.00<br />
AE25<br />
30.00<br />
42.00<br />
46.00<br />
Fuel Inlet<br />
Zone<br />
3.19<br />
3.19<br />
8.12<br />
72.00<br />
Four mounting<br />
holes 0.38" dia.<br />
28.00<br />
29.29<br />
(Alternator End)<br />
24.00<br />
26.14<br />
Electrical<br />
Stub Up<br />
(Alternator End)<br />
20.94<br />
LT0143A30<br />
30.29<br />
LT0143A02<br />
31.25<br />
MN2415<br />
Receiving & <strong>Installation</strong> 3-1