Installation & Operation Manual - Phase-A-Matic, Inc.
Installation & Operation Manual - Phase-A-Matic, Inc.
Installation & Operation Manual - Phase-A-Matic, Inc.
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Appendix D<br />
Series AE25<br />
Information in this Appendix applies to the AE25 Generator.<br />
Operator Panel Configuration<br />
Figure D-1 AE25 Operator Panel<br />
WATER<br />
OIL<br />
HIGH TEMPERATURE<br />
LOW OIL PRESSURE<br />
OVERSPEED<br />
OVERCRANK<br />
Hour Meter<br />
BATTERY<br />
MANUAL<br />
RUN<br />
STOP<br />
MASTER<br />
CONTROL<br />
AUTO<br />
START<br />
DC CONTROL FUSE AC CONTROL FUSE<br />
NAT. GAS<br />
L.P. GAS<br />
Display Lamps<br />
Hour Meter<br />
Meters<br />
DC Control Fuse<br />
AC Control Fuse<br />
High Temperature − Indicates excessive engine coolant temperature.<br />
Low Oil Pressure − Indicates low engine oil pressure.<br />
Overspeed − Indicates engine speed is greater than preset limit.<br />
Overcrank − Failure of the engine to start by the end of the crank period results in<br />
an “overcrank” shutdown and alarm indication.<br />
Displays total hours of operation based on power applied to Fuel Solenoid).<br />
Water − Displays the temperature of the engine coolant.<br />
Oil − Displays the engines oil pressure.<br />
Battery − Displays the battery voltage of the starting battery.<br />
Fuse for engine controller.<br />
Fuse for engine controller.<br />
Master Control Switch<br />
Stop<br />
Stops the Engine and generator set.<br />
<strong>Manual</strong> Run Immediately energizes the crank cycle to start the generator set and produce power.<br />
Auto Start The engine can only be started by making a connection across the remote start terminals of the<br />
control box. This allows normal automatic backup operation of the Generator Set under control of<br />
the Transfer Switch whenever utility AC power is lost.<br />
Natural/LP Gas Selector Switch<br />
Selects the correct fuel source: Natural Gas or L.P. Gas.<br />
MN2415<br />
Series AE25 D-1