Appendix D<br />

Series AE25<br />

Information in this Appendix applies to the AE25 Generator.<br />

Operator Panel Configuration<br />

Figure D-1 AE25 Operator Panel<br />

WATER<br />

OIL<br />

HIGH TEMPERATURE<br />

LOW OIL PRESSURE<br />

OVERSPEED<br />

OVERCRANK<br />

Hour Meter<br />

BATTERY<br />

MANUAL<br />

RUN<br />

STOP<br />

MASTER<br />

CONTROL<br />

AUTO<br />

START<br />

DC CONTROL FUSE AC CONTROL FUSE<br />

NAT. GAS<br />

L.P. GAS<br />

Display Lamps<br />

Hour Meter<br />

Meters<br />

DC Control Fuse<br />

AC Control Fuse<br />

High Temperature − Indicates excessive engine coolant temperature.<br />

Low Oil Pressure − Indicates low engine oil pressure.<br />

Overspeed − Indicates engine speed is greater than preset limit.<br />

Overcrank − Failure of the engine to start by the end of the crank period results in<br />

an “overcrank” shutdown and alarm indication.<br />

Displays total hours of operation based on power applied to Fuel Solenoid).<br />

Water − Displays the temperature of the engine coolant.<br />

Oil − Displays the engines oil pressure.<br />

Battery − Displays the battery voltage of the starting battery.<br />

Fuse for engine controller.<br />

Fuse for engine controller.<br />

Master Control Switch<br />

Stop<br />

Stops the Engine and generator set.<br />

<strong>Manual</strong> Run Immediately energizes the crank cycle to start the generator set and produce power.<br />

Auto Start The engine can only be started by making a connection across the remote start terminals of the<br />

control box. This allows normal automatic backup operation of the Generator Set under control of<br />

the Transfer Switch whenever utility AC power is lost.<br />

Natural/LP Gas Selector Switch<br />

Selects the correct fuel source: Natural Gas or L.P. Gas.<br />

MN2415<br />

Series AE25 D-1