General Wiring Considerations<br />
1. Control wires and Power wires cannot be located in the same conduit (NEC Article 725).<br />
2. When routing the interface wiring, do not route it up against anything that could cut or<br />
chafe the wiring. do not route the wire up against any hot or potentially hot object.<br />
3. Make sure that all the electrical components (generator set, transfer switch, battery<br />
charger, etc.) share a common hardwired ground.<br />
4. Check with your local building inspector to determine what you must do to comply with<br />
the local regulations for grounding of this type of permanent installation.<br />
AE8 Electrical Connections Applies only to AE8 Enclosed and Open Series Generators<br />
Single <strong>Phase</strong> Power Connections<br />
The generator has a 240V single phase AC output. These connections are made at the power<br />
terminal box shown in Figure 3-3.<br />
Figure 3-3 Single <strong>Phase</strong> Output Power Connections<br />
AE8 with Enclosure or Open<br />
Generator<br />
Output<br />
1<br />
N<br />
4<br />
L1<br />
N<br />
L2<br />
Customer<br />
AC Output Connections<br />
(to Transfer Switch)<br />
L1 to N<br />
L2 to N<br />
L1 to L2<br />
120VAC<br />
120VAC<br />
240VAC<br />
BW0120D<br />
Remote Start and Battery Charger Connections<br />
Figure 3-4 shows the connections for the battery charger and the remote start contacts of the<br />
transfer switch. When the Remote Start Switch is closed, the generator will start. The unit will<br />
remain running until this connection is opened. When the Remote Start Switch is opened, the<br />
control circuits allow the engine to run for approximately 60−90 seconds before it shuts off. This<br />
time delay allows the engine to run unloaded to cool down before stopping.<br />
Figure 3-4 Remote Start & Battery Connections<br />
AE8<br />
with Enclosure<br />
AE8<br />
Open<br />
16AWG Customer Provided Optional Equipment<br />
16AWG Customer Provided Optional Equipment<br />
R1<br />
Twisted Pair Wire<br />
Remote Start Switch<br />
Twisted Pair Wire<br />
Remote Start Switch<br />
R2<br />
(Close to Start)<br />
(Close to Start)<br />
Batt+<br />
Out+<br />
Out+<br />
Batt−<br />
Out−<br />
Battery<br />
Out−<br />
Battery<br />
Charger<br />
Charger<br />
D1<br />
+ −<br />
D2<br />
BW0120D<br />
Note:<br />
To 120VAC<br />
(Shore Power)<br />
BW0183D<br />
To 120VAC<br />
(Shore Power)<br />
Connect DK1 and DK2 of the battery charger go to the D1 and D2 terminals of the terminal block if a Master Control Systems <strong>Inc</strong>.<br />
Battery charger is installed. DK1 and DK2 are not polarity sensitive.<br />
Battery<br />
MN2415<br />
Receiving & <strong>Installation</strong> 3-9