Section 4<br />
<strong>Operation</strong><br />
Operator Control Panel<br />
Each operator panel is slightly different, depending on features of the generator you purchased.<br />
The Operator Control Panel of Figure 4-1 is shown because it has most of the available features.<br />
This will be used to explain how the controls operate.<br />
Master Control Switch (Run <strong>Manual</strong> −Off − Remote Auto)<br />
Run <strong>Manual</strong> − Immediately energizes the crank cycle to start<br />
the generator set and produce power.<br />
Stop − Stops the Engine and generator set.<br />
Remote Auto − The engine can only be started by making a connection<br />
across the remote start terminals of the control box.<br />
Allows normal automatic backup operation of the Generator<br />
Set under control of the Transfer Switch whenever utility AC<br />
power is lost.<br />
Controller Fuse<br />
Fuse for engine controller.<br />
Lamp<br />
This Red indicator light will come on when the engine shuts down due to<br />
a fault condition.<br />
Circuit Breaker<br />
Circuit Protection for AC power output.<br />
Circuit Breaker − 2 pole Circuit Protection for the generator set output<br />
windings.<br />
Figure 4-1 Operator Control Panel AE8 and AE10<br />
Master Control<br />
Switch<br />
Controller<br />
Fuse<br />
Lamp<br />
Circuit Breaker<br />
Figure 4-2 Operator Control Panel AE11<br />
Under Speed Shutdown<br />
Alternator Charge Failure Warning<br />
Over Speed Shutdown<br />
Failure to Start Shutdown<br />
High Coolant Temperature Shutdown<br />
Aux1 Input Warn/Shutdown<br />
Low Oil Pressure Shutdown<br />
Aux2 Input Warn/Shutdown<br />
Stop<br />
<strong>Manual</strong><br />
Run<br />
Auto<br />
Start<br />
Hour Meter<br />
(fuel solenoid energized<br />
Shutdown Warning Indicators<br />
Low Oil Pressure, High Coolant Temperature, Over Speed (Engine), Under Speed (Engine),<br />
Failure to Start Engine.<br />
Warning (or Shutdown) Indicators<br />
Alternator Failure (to Charge Battery), Auxiliary 1 Input Active, Auxiliary 2 Input Active.<br />
Hour Meter Displays total hours of operation based on power applied to Fuel Solenoid).<br />
Stop<br />
Stops the Engine and generator set.<br />
<strong>Manual</strong> Run Immediately energizes the crank cycle to start the generator set and produce power.<br />
Auto Start The engine can only be started by making a connection across the remote start terminals of the<br />
control box. This allows normal automatic backup operation of the Generator Set under control of<br />
the Transfer Switch whenever utility AC power is lost.<br />
MN2415<br />
<strong>Operation</strong> 4-1