Section 4<br />

<strong>Operation</strong><br />

Operator Control Panel<br />

Each operator panel is slightly different, depending on features of the generator you purchased.<br />

The Operator Control Panel of Figure 4-1 is shown because it has most of the available features.<br />

This will be used to explain how the controls operate.<br />

Master Control Switch (Run <strong>Manual</strong> −Off − Remote Auto)<br />

Run <strong>Manual</strong> − Immediately energizes the crank cycle to start<br />

the generator set and produce power.<br />

Stop − Stops the Engine and generator set.<br />

Remote Auto − The engine can only be started by making a connection<br />

across the remote start terminals of the control box.<br />

Allows normal automatic backup operation of the Generator<br />

Set under control of the Transfer Switch whenever utility AC<br />

power is lost.<br />

Controller Fuse<br />

Fuse for engine controller.<br />

Lamp<br />

This Red indicator light will come on when the engine shuts down due to<br />

a fault condition.<br />

Circuit Breaker<br />

Circuit Protection for AC power output.<br />

Circuit Breaker − 2 pole Circuit Protection for the generator set output<br />

windings.<br />

Figure 4-1 Operator Control Panel AE8 and AE10<br />

Master Control<br />

Switch<br />

Controller<br />

Fuse<br />

Lamp<br />

Circuit Breaker<br />

Figure 4-2 Operator Control Panel AE11<br />

Under Speed Shutdown<br />

Alternator Charge Failure Warning<br />

Over Speed Shutdown<br />

Failure to Start Shutdown<br />

High Coolant Temperature Shutdown<br />

Aux1 Input Warn/Shutdown<br />

Low Oil Pressure Shutdown<br />

Aux2 Input Warn/Shutdown<br />

Stop<br />

<strong>Manual</strong><br />

Run<br />

Auto<br />

Start<br />

Hour Meter<br />

(fuel solenoid energized<br />

Shutdown Warning Indicators<br />

Low Oil Pressure, High Coolant Temperature, Over Speed (Engine), Under Speed (Engine),<br />

Failure to Start Engine.<br />

Warning (or Shutdown) Indicators<br />

Alternator Failure (to Charge Battery), Auxiliary 1 Input Active, Auxiliary 2 Input Active.<br />

Hour Meter Displays total hours of operation based on power applied to Fuel Solenoid).<br />

Stop<br />

Stops the Engine and generator set.<br />

<strong>Manual</strong> Run Immediately energizes the crank cycle to start the generator set and produce power.<br />

Auto Start The engine can only be started by making a connection across the remote start terminals of the<br />

control box. This allows normal automatic backup operation of the Generator Set under control of<br />

the Transfer Switch whenever utility AC power is lost.<br />

MN2415<br />

<strong>Operation</strong> 4-1