Technical Specification for - Gujarat Electricity Board
Technical Specification for - Gujarat Electricity Board
Technical Specification for - Gujarat Electricity Board
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
TECHNICAL SPECIFICATION FOR<br />
SDH/PDH Equipment with integrated Access Multiplexer<br />
Temperature range:<br />
<strong>for</strong> Ethernet, x DSL, ISDN:<br />
Humidity:<br />
- 5°C … +55°C<br />
max. 95% (no condensation)<br />
g. Mechanical construction<br />
The equipment shall be available as a 19” shelve to be mounted in a 19” rack or 19”<br />
cabinet. It shall be of robust design. All modules shall be integrated in the same shelf.<br />
All connectors shall be accessible from the front and comply with international<br />
specifications. The minimum cabinet depth required shall be stated.<br />
h. Network configuration/management system<br />
The network management system (NMS) shall have facilities to supervise, monitor,<br />
control and configure each equipment and the whole network. It shall have capabilities<br />
of fault, configuration, per<strong>for</strong>mance and security management. It shall provide various<br />
graphical views to the network such as geographical overview, logical network<br />
structure, and hierarchical view. The network management system shall allow to define<br />
different user profiles.<br />
A comprehensive alarm management shall show current alarms such, that icons of the<br />
network elements change their colours according to the alarm level. The alarms shall<br />
be categorized as critical, major, minor alarms and of the warnings and a summary<br />
shall indicate the total number of them in the entire network. An alarm list shall list all<br />
alarms of the entire network according to the time of their occurrence. It shall be<br />
possible to filter alarms with various filter criteria. Operators shall be able to add<br />
comments to the alarms.<br />
The DCN (Data Communication Network) to access all Network Elements shall be<br />
based on TCP-IP. - The management system shall offer an SNMP interface <strong>for</strong> alarm<br />
integration into higher order networks.<br />
i. Local User Terminal<br />
It shall be possible to connect the craft terminal to any Network Element in the network<br />
using the TCP-IP protocol. The craft terminal shall support configuration, maintenance,<br />
and status in<strong>for</strong>mation. It shall provide a ‘windows’ oriented user interface.<br />
j. 1+1 Path protection<br />
The equipment shall provide means to protect 64kBit/s channels. The protection shall<br />
be end to end from one interface (telephone or data) to the other. It shall switch<br />
automatically from the main channel to the standby channel. It shall be configurable<br />
whether the system switches back to the main channel (reversible switching) or not<br />
(non-reversible).<br />
If a path has switched to its standby route because the main route is disturbed this<br />
shall be indicated with an alarm. The switching shall be done within the multiplexer<br />
without using the Network Management System.<br />
k. 1+1 Section protection<br />
The equipment shall provide means to protect STM-1 (MSP). It shall be possible to use<br />
two independent links: one as the main and the other as the standby. The system shall<br />
automatically switch to the standby connection and generate an alarm if the main<br />
connection is disturbed.<br />
Sign & Seal of Bidder<br />
GETCO/E/TS-SDH/PDH FOTE/R1, Dt:16.04.2011<br />
Page 13 of 60