TECHNICAL SPECIFICATION FOR<br />

SDH/PDH Equipment with integrated Access Multiplexer<br />

No Test Name Description Basic<br />

standard<br />

2.8 Damped oscillatory<br />

waves<br />

AC/DC Power supply:<br />

Common mode<br />

Differential mode<br />

Signal terminals:<br />

Common mode<br />

Differential mode<br />

IEC 61000-4-12<br />

Level<br />

2.50kV<br />

1.25kV<br />

2.50kV<br />

1.25kV<br />

Comply (To be<br />

filled up by<br />

bidder)<br />

2.9 Conducted common<br />

mode disturbance<br />

Telecommunication<br />

ports:<br />

Common mode<br />

1 MHz, 400 Hz repetition<br />

rate, 2 s burst duration<br />

Frequency 50 Hz,<br />

continuous mode<br />

2.50kV<br />

IEC 61000-4-16 10 / 30<br />

Vrms<br />

The bidder shall have to comply <strong>for</strong> all the details asked under Clause 2.2.5.6 (A) & (B)<br />

and 2.2.5.7 (c ) and (d) against each items of tables given above invariably. In case of<br />

non-submission of same with the offer, the bid shall be liable to be rejected.<br />

2.2.5.8 Redundancy Requirements and Protection Schemes<br />

Equipment redundancy and Automatic Protection Schemes (APS) are specified in the<br />

Table 2-1. The failure of one element shall not prevent the use of any other that has<br />

not failed.<br />

Table 2.1<br />

Equipment Redundancy Requirements Summary<br />

Fibre Optic terminal equipment :<br />

SDH STM-1 ADM<br />

Power Supply & Converters<br />

Common Control* Cards<br />

APS<br />

APS<br />

* = Common control cards which are<br />

essentially required <strong>for</strong> operation of<br />

the equipment.<br />

The offered equipment shall support at least SNCP as per standard ITU-T G.841. In<br />

case the equipment offered by the Bidder does not support the above mentioned<br />

minimum protection methods, the bidder shall have to provide all additional equipment<br />

needed to provide same level of flexibility, redundancy and functionality at no additional<br />

cost to Employer. The bidders shall provide details of protection schemes supported in<br />

the Bid document.<br />

The offered equipment shall support automatic switchover function between the<br />

redundant modules and all required modules and hardware to support the automatic<br />

switch over shall be provided by the Contractor.<br />

Sign & Seal of Bidder<br />

GETCO/E/TS-SDH/PDH FOTE/R1, Dt:16.04.2011<br />

Page 31 of 60