Please ensure that the new boiler plant is not in circuit when<br />

the flushing takes place, especially if cleansing chemicals are<br />

used to assist the process.<br />

It is important to check the inhibitor concentration after installation,<br />

system modifications, filling the system and every service<br />

in accordance with these instructions.<br />

For the correct dosage and the suitability of inhibitors for use<br />

with our boilers and for further information on water treatment<br />

or system cleaning we advise direct contact with either of the<br />

following companies:<br />

‘F1 ® ’ manufactured by:<br />

Fernox, Cookson Electronics<br />

Forsyth Road<br />

Sheerwater<br />

Woking<br />

Surrey GU21 5RZ<br />

Tel No: 01483 793200<br />

Fax No: 01483 793201<br />

Email: admin@fernox.com<br />

Web site: www.fernox.com<br />

or:<br />

Sentinal ‘X100 ® ’ manufactured by<br />

Sentinel Performance Solutions<br />

The Heath Business & Technical Park<br />

Runcorn<br />

Cheshire,<br />

WA7 4QX<br />

Tel No: 0800 389 4670<br />

Fax No: 0800 389 4677<br />

Email: info.uk@sentinel-solutions.net<br />

Web site: www.sentinel-solutions.net<br />

2.3.5 Safety valve discharge<br />

A pressure relief safety valve is fitted in the boiler set to the<br />

maximum operating pressure of the boiler of 3 bar.<br />

If the pressure in the boiler becomes too high the pressure<br />

is relieved by releasing water to outside via the safety valve<br />

discharge pipe. The discharge pipe should be fitted in accordance<br />

with British Standards and must be at least 15 mm Ø.<br />

The pipe should be positioned so that the discharge of water<br />

or steam is visible and cannot create a hazard to the occupants<br />

of the premises or damage the electric components and<br />

wiring. In addition the discharge should be located where it is<br />

unlikely to cause damage to the premises.<br />

12