<strong>Remeha</strong> <strong>Avanta</strong> <strong>Plus</strong><br />
• Open the boiler gas valve and check the static pressure to<br />
the boiler at the measurement point (C) on the gas block.<br />
C<br />
<br />
The boiler has been factory tested for natural gas at 20 mbar.<br />
The minimum gas inlet pressure is 17 mbar for natural gas<br />
(see 2.4.3).<br />
fi g. 36<br />
LT.AL.W7H.000.039<br />
Measurement point c on the gas block<br />
Check<br />
• Check that the gas supply to the boiler is gas tight (in<br />
compliance with the current regulations, see Chapter 7 the<br />
maximum test pressure at the gas pipe inlet, with the boiler<br />
gas valve open, is 60 mbar.<br />
• Vent the gas pipe by unscrewing the measurement point (C)<br />
on the gas block (tighten it again as soon as the pipe is fully<br />
vented).<br />
• Check that the gas connections in the boiler are sealed.<br />
• Check that all electrical connections, including the earth<br />
connection, have been made correctly.<br />
• Check the electrical connections to the thermostat and other<br />
external controls.<br />
• Check that the flue-gas and air-supply connections are<br />
sealed.<br />
3. Switching the boiler on and setting the controls<br />
• Replace the fuse in the spur and switch on the 230 V power<br />
supply.<br />
• Set the controls to heat demand.<br />
• The boiler will begin an automatic venting-programme<br />
(which lasts approx. 3 minutes) and will do this every time<br />
the power supply is isolated.<br />
• The boiler now starts to run. The operational status is shown<br />
in the display. The normal operating status finally shows 0<br />
in the display.<br />
fi g. 37<br />
112952.LT.GB.W7H.040<br />
Check electrical connections and thermostat<br />
4. Checking/setting the gas/air ratio at full load<br />
The <strong>Avanta</strong> <strong>Plus</strong> boilers are suitable for both natural gas and<br />
propane firing. An optional propane-set is needed (see par.<br />
2.4.2).<br />
The boilers are supplied as standard set for natural gas<br />
230 V<br />
(G20), therefore the following procedure must be carried out<br />
BEFORE the boilers are fired and commissioned for the first<br />
time on propane:<br />
- Fit propane set (instruction in kit);<br />
- adjust the fan speed (for procedure; see Par. 2.9.8, for values;<br />
see table 06 and table 08) and;<br />
- adjust the gas/air ratio (for values; see table 06 and table<br />
08).<br />
fi g. 38<br />
112952.LT.GB.W7H.041<br />
Power on and controls on heat demand<br />