<strong>Remeha</strong> <strong>Avanta</strong> <strong>Plus</strong><br />

To be changed by installer only<br />

p 27<br />

p 28<br />

p 29<br />

p 30<br />

P 31<br />

p d f<br />

(p d U<br />

is shown<br />

later)<br />

Heat curve set point<br />

flow temperature<br />

Heat curve set point<br />

outside temperature (min)<br />

Heat curve set point<br />

outside temperature (max)<br />

Boiler type<br />

DHW control stop<br />

Restore factory settings<br />

0 - 60 °C 20<br />

0 - 30 °C 20<br />

-40 - 0 °C - 15**<br />

0 = combi<br />

1 = system<br />

0 - 20 °C 15<br />

On identification plate d f setting X<br />

is shown. Change parameter into X will<br />

restore the factory settings, see par. 2.9.10<br />

On identification plate d U setting Y<br />

is shown. Change parameter into Y will<br />

restore the factory settings, see par. 2.9.10<br />

0<br />

X<br />

Y<br />

table 09 Settings at service level<br />

1<br />

) Do not exceed this value<br />

* the system boiler in combination with an external calorifier will not warm up the calorifier in the Eco-mode.<br />

** minus character is not shown in display<br />

*** only change for propane firing<br />

Can also be changed by users<br />

Codes in display<br />

To be changed by installer only<br />

Description<br />

Setting range and notes where<br />

applicable<br />

Factory settings<br />

18s 24s 30s<br />

p 1 T set<br />

flow 20 - 85°C 75°C<br />

p 2 T set<br />

DHW 40 - 65°C 55°C<br />

p 3 Boiler regulation<br />

0 = CH off<br />

and DHW off<br />

1 = CH on<br />

and DHW on<br />

2 = CH on<br />

and DHW off<br />

3 = CH off<br />

and DHW on<br />

2<br />

p 4 Eco or comfort setting<br />

p 5 Anticipated current<br />

0 = comfort setting<br />

1 = eco mode*<br />

2 = regulated by controller<br />

0 = no anticipated current<br />

for thermostat on/off<br />

1 = anticipated current<br />

for thermostat on/off<br />

p 6 Display off automatically<br />

1 = display stays on<br />

2 = displaylight switches off automatically<br />

2<br />

0 = display stays off<br />

after 3 minutes<br />

p 17<br />

Maximum fan speed CH 10 – 70<br />

(natural gas)<br />

x 100 rpm<br />

35 1 ) 37 1 ) 52 1 )<br />

Maximum fan speed CH 10 – 70<br />

(propane)<br />

x 100 rpm<br />

33 1 ) 35 1 ) 50 1 )<br />

Maximum fan speed DHW<br />

(natural gas)<br />

Do not change *** 35 1 ) 43 1 ) 52 1 )<br />

p 18<br />

p 19<br />

Maximum fan speed DHW<br />

(propane)<br />

Minimum fan speed<br />

(CH and DHW)<br />

(natural gas)<br />

Minimum fan speed<br />

(CH and DHW)<br />

(propane)<br />

Adjustments for<br />

propane firing<br />

2<br />

0<br />

33 1 ) 41 1 ) 50 1 )<br />

Do not change *** 13<br />

Adjustments for<br />

propane firing<br />

20<br />

38