If the DHW water temperature on the OpenTherm ® control can<br />
be adjusted, then the <strong>Remeha</strong> <strong>Avanta</strong> <strong>Plus</strong> will supply water<br />
at the temperature determined on the OpenTherm ® with the<br />
maximum being set in the boiler.<br />
OpenTherm ® is an industry standard modulating control available<br />
from several control manufacturers.<br />
<br />
The <strong>Remeha</strong> <strong>Avanta</strong> <strong>Plus</strong> can therefore be controlled directly<br />
by any other controls with this OpenTherm ® logo<br />
Exist<br />
links<br />
fi g. 24<br />
Terminal<br />
Block X9<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
8<br />
Outside sensor (red band) for direct boiler weather compensation<br />
or when used in conjuction with a compatable Open Therm<br />
control eg: Chronotherm or Celcia 20<br />
X9<br />
Wiring diagram outside temperature sensor<br />
2.7.5 Connecting an outside temperature sensor<br />
An outside temperature sensor can be connected to connectors<br />
1 and 2 of the X9 terminal block.<br />
The boiler will regulate the output using the set point of the<br />
internal heat curve.<br />
This can be set as follows:<br />
- Outside temperature minimum set point = -15°C (adjustable<br />
with parameter p29 to between 0 and -30°C)<br />
- Outside temperature maximum set point = 20°C (adjustable<br />
with parameter p28 to between 0 and 40°C)<br />
- Flow temperature set point at maximum outside temperature<br />
= 20°C (adjustable with parameter p27 to between<br />
0 and 60°C)<br />
- Flow temperature set point at minimum outside temperature<br />
= 20°C (adjustable with parameter p1 to between<br />
20 and 85°C)<br />
LT.AL.W7H.000.029e<br />
75<br />
60<br />
40<br />
Factory setting<br />
<br />
An outside sensor used in conjunction with a simple 230 V<br />
time clock will provide easy to set up and operate - timed<br />
weather compensation heating based on the above graph.<br />
20<br />
-15<br />
0 10 20<br />
fi g. 25<br />
Heat curve <strong>Remeha</strong> <strong>Avanta</strong> <strong>Plus</strong><br />
LT.AL.W7H.000.030<br />