<strong>Remeha</strong> <strong>Avanta</strong> <strong>Plus</strong><br />

If the DHW water temperature on the OpenTherm ® control can<br />

be adjusted, then the <strong>Remeha</strong> <strong>Avanta</strong> <strong>Plus</strong> will supply water<br />

at the temperature determined on the OpenTherm ® with the<br />

maximum being set in the boiler.<br />

OpenTherm ® is an industry standard modulating control available<br />

from several control manufacturers.<br />

<br />

The <strong>Remeha</strong> <strong>Avanta</strong> <strong>Plus</strong> can therefore be controlled directly<br />

by any other controls with this OpenTherm ® logo<br />

Exist<br />

links<br />

fi g. 24<br />

Terminal<br />

Block X9<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

Outside sensor (red band) for direct boiler weather compensation<br />

or when used in conjuction with a compatable Open Therm<br />

control eg: Chronotherm or Celcia 20<br />

X9<br />

Wiring diagram outside temperature sensor<br />

2.7.5 Connecting an outside temperature sensor<br />

An outside temperature sensor can be connected to connectors<br />

1 and 2 of the X9 terminal block.<br />

The boiler will regulate the output using the set point of the<br />

internal heat curve.<br />

This can be set as follows:<br />

- Outside temperature minimum set point = -15°C (adjustable<br />

with parameter p29 to between 0 and -30°C)<br />

- Outside temperature maximum set point = 20°C (adjustable<br />

with parameter p28 to between 0 and 40°C)<br />

- Flow temperature set point at maximum outside temperature<br />

= 20°C (adjustable with parameter p27 to between<br />

0 and 60°C)<br />

- Flow temperature set point at minimum outside temperature<br />

= 20°C (adjustable with parameter p1 to between<br />

20 and 85°C)<br />

LT.AL.W7H.000.029e<br />

75<br />

60<br />

40<br />

Factory setting<br />

<br />

An outside sensor used in conjunction with a simple 230 V<br />

time clock will provide easy to set up and operate - timed<br />

weather compensation heating based on the above graph.<br />

20<br />

-15<br />

0 10 20<br />

fi g. 25<br />

Heat curve <strong>Remeha</strong> <strong>Avanta</strong> <strong>Plus</strong><br />