simatic s7-400 - Teknika Otomasyon
simatic s7-400 - Teknika Otomasyon
simatic s7-400 - Teknika Otomasyon
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
SIMATIC S7-<strong>400</strong><br />
Communication<br />
© Siemens AG 2008<br />
CP 441-1, CP 441-2<br />
5<br />
■ Overview<br />
• For powerful, high-speed serial communication via point-topoint<br />
connections<br />
• 2 versions:<br />
- CP 441-1 with 1 variable interface for simple point-to-point<br />
connection<br />
- CP 441-2 with 2 variable interfaces for powerful point-topoint<br />
connection<br />
• Plug-in interface modules for different transmission interfaces:<br />
RS 232C (V.24) , 20 mA (TTY) or RS 422/RS 485 (X.27)<br />
• Implemented protocols: ASCII, 3964 (R), printer drivers;<br />
CP 441-2 additionally has RK 512 and customized protocols<br />
(retrofittable)<br />
• Simple parameterization via a parameterization tool integrated<br />
into STEP 7<br />
■ Technical specifications<br />
6ES7 441-1AA04-<br />
0AE0<br />
Supply voltages<br />
Rated value<br />
• DC 5 V Yes Yes<br />
• DC 24 V Yes Yes<br />
Current consumption<br />
from backplane bus DC 5 V,<br />
max.<br />
Current consumption/<br />
power loss<br />
600 mA; without<br />
interface module<br />
Power loss, typ. 0.3 W 0.3 W<br />
Memory<br />
Type of storage<br />
Memory requirements per<br />
interface in CompactFlash<br />
Card of S7-CPU<br />
1 to 5 KB for parameters;<br />
0 to 55 KB for<br />
message texts<br />
6ES7 441-2AA04-<br />
0AE0<br />
600 mA; without<br />
interface module<br />
1 to 5 KB for parameters;<br />
0 to 55 KB for<br />
message texts;<br />
0 to 64 KB for<br />
loadable drivers<br />
interfaces<br />
Number of interfaces 1; variable 2; variable<br />
Physical interface,<br />
Yes<br />
Yes<br />
20mA (TTY)<br />
interface physics,<br />
Yes<br />
Yes<br />
RS 232C (V.24)<br />
interface physics,<br />
Yes<br />
Yes<br />
RS 422/RS 485 (X.27)<br />
20mA (TTY), cable length, 1 000 m 1 000 m<br />
shielded, max.<br />
RS 232, cable length, 10 m 10 m<br />
shielded, max.<br />
RS 422/485, cable length, 1 200 m 1 200 m<br />
shielded, max.<br />
interface module<br />
• 20 mA (TTY),<br />
power consumption from<br />
5 V/24 V, max.<br />
• RS 422/485 (X.27),<br />
power consumption from<br />
5V, max.<br />
• RS 232C (V.24),<br />
power consumption from<br />
5V, max.<br />
100 mA; 100 mA<br />
from 5 V;<br />
45 mA from 24 V<br />
300 mA at 5 V;<br />
45 mA at 24 V<br />
250 mA; from 5 V 300 mA<br />
100 mA; from 5V 300 mA<br />
Point-to-point<br />
supported printers<br />
6ES7 441-1AA04-<br />
0AE0<br />
HP-Deskjet,<br />
HP-Laserjet,<br />
IBM-Proprinter,<br />
user-defined<br />
6ES7 441-2AA04-<br />
0AE0<br />
HP-Deskjet,<br />
HP-Laserjet,<br />
IBM-Proprinter,<br />
user-defined<br />
Transmission speed, max. 38.4 kBit/s 115.2 kBit/s;<br />
distributed on both<br />
interfaces<br />
Integrated protocol driver<br />
• 3964 (R) Yes Yes<br />
•ASCII Yes Yes<br />
• Printer Yes Yes<br />
• customer-specific drivers No<br />
Yes<br />
reloadable<br />
• RK512 No Yes<br />
Transmission speed,<br />
20 mA (TTY)<br />
• with 3964 (R) protocol, 19.2 kBit/s 19.2 kBit/s<br />
max.<br />
• with ASCII protocol, max. 19.2 kBit/s 19.2 kBit/s<br />
• with printer driver, max., 19.2 kBit/s 19.2 kBit/s<br />
• with RK 512 protocol, max.<br />
19.2 kBit/s<br />
Transmission speed,<br />
RS 422/485<br />
• with 3964 (R) protocol, 38.4 kBit/s 115.2 kBit/s<br />
max.<br />
• with ASCII protocol, max. 38.4 kBit/s 115.2 kBit/s<br />
• with printer driver, max. 38.4 kBit/s 115.2 kBit/s<br />
• with RK 512 protocol, max.<br />
115.2 kBit/s<br />
Transmission speed, RS232<br />
• with 3964 (R) protocol, 38.4 kBit/s 115.2 kBit/s<br />
max.<br />
• with ASCII protocol, max. 38.4 kBit/s 115.2 kBit/s<br />
• with printer driver, max., 38.4 kBit/s 115.2 kBit/s<br />
• with RK 512 protocol, max.<br />
115.2 kBit/s<br />
5/106 Siemens ST 70 · 2009