© Siemens AG 2008<br />

SIMATIC S7-<strong>400</strong><br />

Central processing units<br />

■ Technical specifications (continued)<br />

6ES7 416-2FN05-<br />

0AB0<br />

6ES7 416-3FR05-<br />

0AB0<br />

S7 counter (continued)<br />

• Remanence<br />

- adjustable Yes Yes<br />

- lower limit 0 0<br />

- upper limit 2 047 2 047<br />

- preset From Z 0 to Z 7 From Z 0 to Z 7<br />

• Counting range<br />

- lower limit 0 0<br />

- upper limit 999 999<br />

IEC counter<br />

• present Yes Yes<br />

• Type SFB SFB<br />

S7 times<br />

• Number 2 048 2 048<br />

• Remanence<br />

- adjustable Yes Yes<br />

- lower limit 0 0<br />

- upper limit 2 047 2 047<br />

- preset No times retentive No times retentive<br />

• Time range<br />

- lower limit 10 ms 10 ms<br />

- upper limit 9 990 s 9 990 s<br />

IEC timer<br />

• present Yes Yes<br />

• Type SFB SFB<br />

Data areas and their<br />

remanence<br />

remanent data area, total Total working and<br />

load memory (with<br />

backup battery)<br />

Total working and<br />

load memory (with<br />

backup battery)<br />

Flag<br />

• Number, max. 16 Kibyte 16 Kibyte<br />

• Remanence available Yes Yes<br />

• Number of clock memories 8; (in 1 memory<br />

byte)<br />

Address area<br />

I/O address area<br />

8; (in 1 memory<br />

byte)<br />

• Inputs 16 Kibyte 16 Kibyte<br />

•Outputs 16 Kibyte 16 Kibyte<br />

• of which, distributed<br />

- MPI/DPinterface, inputs 2Kibyte 2Kibyte<br />

- MPI/DP interface, 2Kibyte<br />

2Kibyte<br />

outputs<br />

- DP interface, inputs 8Kibyte 8Kibyte<br />

- DP interface, outputs 8Kibyte 8Kibyte<br />

Process image<br />

• Inputs, adjustable 16 Kibyte 16 Kibyte<br />

• Outputs, adjustable 16 Kibyte 16 Kibyte<br />

• Inputs, preset 512 byte 512 byte<br />

• Outputs, preset 512 byte 512 byte<br />

• consistent data, max. 244 byte 244 byte<br />

• Access to consistent data<br />

in process image<br />

Yes<br />

Yes<br />

6ES7 416-2FN05-<br />

0AB0<br />

CPU 416F<br />

6ES7 416-3FR05-<br />

0AB0<br />

Subprocess images<br />

• Number of subprocess 15 15<br />

images, max.<br />

Digital channels<br />

• Inputs 131 072 131 072<br />

•Outputs 131 072 131 072<br />

• Inputs, of which central 131 072 131 072<br />

• Outputs, of which central 131 072 131 072<br />

Analog channels<br />

• Inputs 8 192 8 192<br />

•Outputs 8 192 8 192<br />

• Inputs, of which central 8 192 8 192<br />

• Outputs, of which central 8 192 8 192<br />

Hardware config.<br />

connectable OPs 63 63<br />

Central devices, max. 1 1<br />

Expansion devices, max. 21 21<br />

Multicomputing<br />

Yes; Max. 4 CPUs<br />

(with UR1 or UR2)<br />

Yes; Max. 4 CPUs<br />

(with UR1 or UR2)<br />

IM<br />

• Number of connectable 6 6<br />

IMs (total), max.<br />

• Number of connectable 6 6<br />

IM 460s, max.<br />

• Number of connectable 4; IM 463-2 4; IM 463-2<br />

IM 463s, max.<br />

Number of DP masters<br />

• integrated 2 2<br />

• via IM 467 4 4<br />

•via CP 10; CP 443-5<br />

Extended<br />

• Mixed mode IM + CP<br />

permitted<br />

No; IM 467 cannot<br />

be used with<br />

CP 443-5 Ext.;<br />

IM 467 cannot be<br />

used with<br />

CP 443-1 EX40 in<br />

PN IO mode<br />

• via interface module 0 1<br />

• Number of pluggable 6 6<br />

S5 modules (via adapter<br />

capsule in central device),<br />

max.<br />

Number of IO controllers<br />

• integrated<br />

•via CP 4;<br />

Via CP 443-1 EX 41<br />

in PN mode; max. 4<br />

in central controller<br />

Number of operable FMs<br />

and CPs (recommended)<br />

•FM<br />

Limited due to<br />

number of slots and<br />

number of connections<br />

10; CP 443-5<br />

Extended<br />

No; IM 467 cannot<br />

be used with<br />

CP 443-5 Ext.;<br />

IM 467 cannot be<br />

used with<br />

CP 443-1 EX40 in<br />

PN IO mode<br />

4;<br />

Via CP 443-1 EX 41<br />

in PN mode; max. 4<br />

in central controller<br />

Limited due to<br />

number of slots and<br />

number of connections<br />

5<br />

Siemens ST 70 · 2009<br />

5/49