SIMATIC S7-<strong>400</strong><br />

Modules for SIMATIC S7-<strong>400</strong>H<br />

© Siemens AG 2008<br />

Y link for S7-<strong>400</strong>H<br />

■ Overview<br />

• Transceiver for the transition from a redundant PROFIBUS DP<br />

master system to a single-channel PROFIBUS DP master<br />

system<br />

• To connect devices with a single PROFIBUS DP interface to<br />

the redundant PROFIBUS DP master system of the SIMATIC<br />

S7-<strong>400</strong>H<br />

5<br />

■ Technical specifications<br />

6ES7 153-2BA02-0XB0<br />

Supply voltages<br />

Rated value<br />

• Permissible range (ripple 20.4 V<br />

included), lower limit (DC)<br />

• permissible range (ripple 28.8 V<br />

included), upper limit (DC)<br />

Power supply and voltage<br />

jumpering<br />

• Mains/voltage failure<br />

20 ms<br />

jumpering<br />

Voltages and currents<br />

external protection for supply 2.5 A<br />

cables (recommendation)<br />

Current consumption<br />

Inrush current, typ.<br />

3A<br />

I²t<br />

0.1 A²s<br />

Current consumption, max. 600 mA<br />

Power loss, typ.<br />

5.5 W<br />

Address area<br />

Adressing volume<br />

•Outputs<br />

244 byte<br />

• Inputs<br />

244 byte<br />

Hardware config.<br />

Number of modules per DP 12<br />

slave interface, max.<br />

interfaces<br />

PROFIBUS DP, Output current, 70 mA<br />

max.<br />

interface physics, RS 485 Yes<br />

PROFIBUS DP<br />

Transmission procedure RS 485<br />

Transmission speed, max. 12 MBit/s<br />

Node addresses 1...125<br />

SYNC capability<br />

Yes<br />

FREECE capability<br />

Yes<br />

direct data exchange<br />

Yes; Sender<br />

(cross traffic)<br />

6ES7 153-2BA02-0XB0<br />

1st interface<br />

DP slave<br />

• GSD file<br />

SI04801.GSG<br />

CPU/programming<br />

Configuration software<br />

•STEP 7 Yes; STEP 7 / COM PROFIBUS /<br />

non-Siemens tools via GSD file<br />

Time stamping<br />

Accuracy<br />

1 ms; 1ms at up to 8 modules;<br />

10ms at up to 12 modules<br />

Number of stampable digital<br />

inputs, max.<br />

Time format RFC 1119<br />

Time resolution<br />

0.466 ns<br />

Time stamp on signal change Yes<br />

Environmental requirements<br />

Operating termperature<br />

•min. 0°C<br />

• max. 60 °C<br />

Air pressure<br />

• Operating height above sea 3.000 m<br />

level, max.<br />

Degree and class of protection<br />

•IP 20<br />

Yes<br />

General information<br />

Vendor identification (VendorID) 801E<br />

Dimensions<br />

Dimensions<br />

Width<br />

40 mm<br />

Height<br />

125 mm<br />

Depth<br />

117 mm<br />

Weights<br />

Weight, approx.<br />

360 g<br />

128; Max. 128 signals / station;<br />

max. 32 signals / slot<br />

5/120 Siemens ST 70 · 2009