simatic s7-400 - Teknika Otomasyon
simatic s7-400 - Teknika Otomasyon
simatic s7-400 - Teknika Otomasyon
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
SIMATIC S7-<strong>400</strong><br />
Modules for SIMATIC S7-<strong>400</strong>H<br />
© Siemens AG 2008<br />
Y link for S7-<strong>400</strong>H<br />
■ Overview<br />
• Transceiver for the transition from a redundant PROFIBUS DP<br />
master system to a single-channel PROFIBUS DP master<br />
system<br />
• To connect devices with a single PROFIBUS DP interface to<br />
the redundant PROFIBUS DP master system of the SIMATIC<br />
S7-<strong>400</strong>H<br />
5<br />
■ Technical specifications<br />
6ES7 153-2BA02-0XB0<br />
Supply voltages<br />
Rated value<br />
• Permissible range (ripple 20.4 V<br />
included), lower limit (DC)<br />
• permissible range (ripple 28.8 V<br />
included), upper limit (DC)<br />
Power supply and voltage<br />
jumpering<br />
• Mains/voltage failure<br />
20 ms<br />
jumpering<br />
Voltages and currents<br />
external protection for supply 2.5 A<br />
cables (recommendation)<br />
Current consumption<br />
Inrush current, typ.<br />
3A<br />
I²t<br />
0.1 A²s<br />
Current consumption, max. 600 mA<br />
Power loss, typ.<br />
5.5 W<br />
Address area<br />
Adressing volume<br />
•Outputs<br />
244 byte<br />
• Inputs<br />
244 byte<br />
Hardware config.<br />
Number of modules per DP 12<br />
slave interface, max.<br />
interfaces<br />
PROFIBUS DP, Output current, 70 mA<br />
max.<br />
interface physics, RS 485 Yes<br />
PROFIBUS DP<br />
Transmission procedure RS 485<br />
Transmission speed, max. 12 MBit/s<br />
Node addresses 1...125<br />
SYNC capability<br />
Yes<br />
FREECE capability<br />
Yes<br />
direct data exchange<br />
Yes; Sender<br />
(cross traffic)<br />
6ES7 153-2BA02-0XB0<br />
1st interface<br />
DP slave<br />
• GSD file<br />
SI04801.GSG<br />
CPU/programming<br />
Configuration software<br />
•STEP 7 Yes; STEP 7 / COM PROFIBUS /<br />
non-Siemens tools via GSD file<br />
Time stamping<br />
Accuracy<br />
1 ms; 1ms at up to 8 modules;<br />
10ms at up to 12 modules<br />
Number of stampable digital<br />
inputs, max.<br />
Time format RFC 1119<br />
Time resolution<br />
0.466 ns<br />
Time stamp on signal change Yes<br />
Environmental requirements<br />
Operating termperature<br />
•min. 0°C<br />
• max. 60 °C<br />
Air pressure<br />
• Operating height above sea 3.000 m<br />
level, max.<br />
Degree and class of protection<br />
•IP 20<br />
Yes<br />
General information<br />
Vendor identification (VendorID) 801E<br />
Dimensions<br />
Dimensions<br />
Width<br />
40 mm<br />
Height<br />
125 mm<br />
Depth<br />
117 mm<br />
Weights<br />
Weight, approx.<br />
360 g<br />
128; Max. 128 signals / station;<br />
max. 32 signals / slot<br />
5/120 Siemens ST 70 · 2009