SIMATIC S7-<strong>400</strong><br />
Central processing units<br />
CPU 412H, CPU 414H, CPU 417H<br />
■ Technical specifications (continued)<br />
Process image<br />
6ES7 412-3HJ14-0AB0 6ES7 414-4HM14-0AB0 6ES7 417-4HT14-0AB0<br />
• Inputs, adjustable 8 Kibyte 8Kibyte 16 Kibyte<br />
• Outputs, adjustable 8 Kibyte 8Kibyte 16 Kibyte<br />
• Inputs, preset 256 byte 256 byte 1024byte<br />
• Outputs, preset 256 byte 256 byte 1024byte<br />
• consistent data, max. 244 byte 244 byte 244 byte<br />
• Access to consistent data in<br />
process image<br />
Subprocess images<br />
• Number of subprocess<br />
images, max.<br />
Digital channels<br />
Yes Yes Yes<br />
15 15 15<br />
• Inputs 65 536 65 536 131 072<br />
•Outputs 65 536 65 536 131 072<br />
• Inputs, of which central 65 536 65 536 131 072<br />
• Outputs, of which central 65 536 65 536 131 072<br />
Analog channels<br />
• Inputs 4 096 4 096 8192<br />
•Outputs 4 096 4 096 8192<br />
• Inputs, of which central 4 096 4 096 8192<br />
• Outputs, of which central 4 096 4 096 8192<br />
Hardware config.<br />
connectable OPs<br />
15 without message processing,<br />
8 with message processing<br />
31 without message processing,<br />
8 with message processing<br />
63 without message processing,<br />
16 with message processing<br />
Central devices, max. 1 1 1<br />
Expansion devices, max. 21 21 21<br />
Multicomputing No No No<br />
IM<br />
• Number of connectable IMs 6 6 6<br />
(total), max.<br />
• Number of connectable 6 6 6<br />
IM 460s, max.<br />
• Number of connectable 4; Single mode only 4; Single mode only 4; Single mode only<br />
IM 463s, max.<br />
Number of DP masters<br />
• integrated 1 2 2<br />
• via CP 10 10 10<br />
• Mixed mode IM + CP permitted No No No<br />
• via interface module 0<br />
Number of operable FMs and<br />
CPs (recommended)<br />
•FM<br />
See manual Automation System<br />
S7-<strong>400</strong>H fault-tolerant systems.<br />
Limited due to number of slots and<br />
number of connections<br />
See manual Automation System<br />
S7-<strong>400</strong>H fault-tolerant systems.<br />
Limited due to number of slots and<br />
number of connections<br />
See manual Automation System<br />
S7-<strong>400</strong>H fault-tolerant systems.<br />
Limited due to number of slots and<br />
number of connections<br />
• CP, point-to-point<br />
See manual Automation System<br />
S7-<strong>400</strong>H fault-tolerant systems.<br />
Limited due to number of slots and<br />
number of connections<br />
• PROFIBUS and Ethernet CPs 14;<br />
Of which max. 10 CP as DP master<br />
See manual Automation System<br />
S7-<strong>400</strong>H fault-tolerant systems.<br />
Limited due to number of slots and<br />
number of connections<br />
14;<br />
Of which max. 10 CP as DP master<br />
See manual Automation System<br />
S7-<strong>400</strong>H fault-tolerant systems.<br />
Limited due to number of slots and<br />
number of connections<br />
14;<br />
Of which max. 10 CP as DP master<br />
5<br />
Siemens ST 70 · 2009<br />