11.01.2015 Views

simatic s7-400 - Teknika Otomasyon

simatic s7-400 - Teknika Otomasyon

simatic s7-400 - Teknika Otomasyon

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

© Siemens AG 2008<br />

SIMATIC S7-<strong>400</strong><br />

Central processing units<br />

CPU 412H, CPU 414H, CPU 417H<br />

■ Technical specifications (continued)<br />

Process image<br />

6ES7 412-3HJ14-0AB0 6ES7 414-4HM14-0AB0 6ES7 417-4HT14-0AB0<br />

• Inputs, adjustable 8 Kibyte 8Kibyte 16 Kibyte<br />

• Outputs, adjustable 8 Kibyte 8Kibyte 16 Kibyte<br />

• Inputs, preset 256 byte 256 byte 1024byte<br />

• Outputs, preset 256 byte 256 byte 1024byte<br />

• consistent data, max. 244 byte 244 byte 244 byte<br />

• Access to consistent data in<br />

process image<br />

Subprocess images<br />

• Number of subprocess<br />

images, max.<br />

Digital channels<br />

Yes Yes Yes<br />

15 15 15<br />

• Inputs 65 536 65 536 131 072<br />

•Outputs 65 536 65 536 131 072<br />

• Inputs, of which central 65 536 65 536 131 072<br />

• Outputs, of which central 65 536 65 536 131 072<br />

Analog channels<br />

• Inputs 4 096 4 096 8192<br />

•Outputs 4 096 4 096 8192<br />

• Inputs, of which central 4 096 4 096 8192<br />

• Outputs, of which central 4 096 4 096 8192<br />

Hardware config.<br />

connectable OPs<br />

15 without message processing,<br />

8 with message processing<br />

31 without message processing,<br />

8 with message processing<br />

63 without message processing,<br />

16 with message processing<br />

Central devices, max. 1 1 1<br />

Expansion devices, max. 21 21 21<br />

Multicomputing No No No<br />

IM<br />

• Number of connectable IMs 6 6 6<br />

(total), max.<br />

• Number of connectable 6 6 6<br />

IM 460s, max.<br />

• Number of connectable 4; Single mode only 4; Single mode only 4; Single mode only<br />

IM 463s, max.<br />

Number of DP masters<br />

• integrated 1 2 2<br />

• via CP 10 10 10<br />

• Mixed mode IM + CP permitted No No No<br />

• via interface module 0<br />

Number of operable FMs and<br />

CPs (recommended)<br />

•FM<br />

See manual Automation System<br />

S7-<strong>400</strong>H fault-tolerant systems.<br />

Limited due to number of slots and<br />

number of connections<br />

See manual Automation System<br />

S7-<strong>400</strong>H fault-tolerant systems.<br />

Limited due to number of slots and<br />

number of connections<br />

See manual Automation System<br />

S7-<strong>400</strong>H fault-tolerant systems.<br />

Limited due to number of slots and<br />

number of connections<br />

• CP, point-to-point<br />

See manual Automation System<br />

S7-<strong>400</strong>H fault-tolerant systems.<br />

Limited due to number of slots and<br />

number of connections<br />

• PROFIBUS and Ethernet CPs 14;<br />

Of which max. 10 CP as DP master<br />

See manual Automation System<br />

S7-<strong>400</strong>H fault-tolerant systems.<br />

Limited due to number of slots and<br />

number of connections<br />

14;<br />

Of which max. 10 CP as DP master<br />

See manual Automation System<br />

S7-<strong>400</strong>H fault-tolerant systems.<br />

Limited due to number of slots and<br />

number of connections<br />

14;<br />

Of which max. 10 CP as DP master<br />

5<br />

Siemens ST 70 · 2009<br />

5/41