11.01.2015 Views

simatic s7-400 - Teknika Otomasyon

simatic s7-400 - Teknika Otomasyon

simatic s7-400 - Teknika Otomasyon

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

© Siemens AG 2008<br />

SIMATIC S7-<strong>400</strong><br />

Analog modules<br />

SM 431 analog input modules<br />

■ Technical specifications (continued)<br />

6ES7 431-7QH00-0AB0 6ES7 431-7KF00-0AB0 6ES7 431-7KF10-0AB0<br />

Input ranges (rated values),<br />

resistance thermometers<br />

• Ni 100 Yes Yes<br />

• Ni 1000 Yes Yes; Different characteristics<br />

selectable: Europe/U.S<br />

• Pt 100 Yes Yes<br />

• Pt 1000 Yes Yes<br />

• Pt 200 Yes Yes<br />

• Pt 500 Yes Yes<br />

Input ranges (rated values),<br />

resistors<br />

• 0 to 150 Ohm<br />

Yes<br />

• 0 to 300 Ohm<br />

Yes<br />

• 0 to 48 Ohm<br />

Yes<br />

• 0 to 600 Ohm<br />

Yes<br />

• 0 to 6000 Ohm<br />

Yes; usable up to 5000 ohms<br />

• permissible input frequency for<br />

voltage input (destruction<br />

limit), max.<br />

18 V; 18 V continuous,<br />

75 V for 1 ms<br />

(mark to space ratio 1:20)<br />

35 V; 35 V continuous,<br />

75 V for max. 1 s<br />

(mark to space ratio 1:20)<br />

• permissible input current for 40 mA 32 mA<br />

current input (destruction limit),<br />

max.<br />

Characteristic curve linearization<br />

• programmable Yes Yes Yes<br />

- for thermoelements Type B, E, J, K, L, N, R, S, T, U Type B, E, J, K, L, N, R, S, T, U<br />

- for thermoresistor Pt100, Pt200, Pt500, Pt1000, Ni100,<br />

Ni1000<br />

35 V; 35 V continuous,<br />

75 V for max. 1 s<br />

(mark to space ratio 1:20)<br />

Temperature compensation<br />

• internal temperature compensation<br />

Yes<br />

Yes<br />

• external temperature compensation<br />

Yes<br />

with compensations<br />

socket<br />

• external temperature compensation<br />

Yes<br />

with Pt100<br />

• dynamic reference temperature<br />

Yes<br />

Yes<br />

value<br />

Analog value creation<br />

Integration and conversion<br />

time/resolution per channel<br />

• Resolution with overload area 16 Bit; 16 / 16 / 16 16 Bit 16 Bit<br />

(bit including sign), max.<br />

• Integration time, parameterizable<br />

Yes Yes Yes<br />

• Basic conversion time, ms 2.5 / 16.7 / 20 ms 2.5 / 16.7 / 20 / 100 8 / 23 / 25 ms<br />

Pt100, Pt200, Pt500, Pt1000, Ni100,<br />

Ni1000; different characteristics<br />

selectable (Europe/U.S.)<br />

5<br />

Siemens ST 70 · 2009<br />

5/75