simatic s7-400 - Teknika Otomasyon
simatic s7-400 - Teknika Otomasyon
simatic s7-400 - Teknika Otomasyon
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
© Siemens AG 2008<br />
SIMATIC S7-<strong>400</strong><br />
Central processing units<br />
CPU 412H, CPU 414H, CPU 417H<br />
■ Technical specifications (continued)<br />
S5-compatible communication<br />
• supported<br />
6ES7 412-3HJ14-0AB0 6ES7 414-4HM14-0AB0 6ES7 417-4HT14-0AB0<br />
Yes; (via CP -max. 10- and<br />
FC AG_SEND and FC AG_RECV)<br />
Yes; (via CP -max. 10- and<br />
FC AG_SEND and FC AG_RECV)<br />
Yes; (via CP -max. 10-<br />
and FC AG_SEND and FC<br />
AG_RECV)<br />
• Useful data per job, max. 8 Kibyte 8Kibyte 8 Kibyte<br />
Standard communication (FMS)<br />
• supported Yes; Via CP and loadable FB Yes; Via CP and loadable FB Yes; Via CP and loadable FB<br />
Number of connections<br />
• overall 16 32 64<br />
1st interface<br />
Physics RS 485 / PROFIBUS + MPI RS 485 / PROFIBUS + MPI RS 485 / PROFIBUS + MPI<br />
isolated Yes Yes Yes<br />
Functionality<br />
•MPI Yes Yes Yes<br />
• DP master Yes Yes Yes<br />
• DP slave No No No<br />
MPI<br />
• Number of connections 16 32 44<br />
• Services<br />
- PG/OP communication Yes Yes Yes<br />
- Routing Yes Yes Yes<br />
- Global data communication No No No<br />
- S7 basic communication No No No<br />
- S7 communication Yes Yes Yes<br />
• Transmission speeds, max. 12 MBit/s 12 MBit/s 12 MBit/s<br />
DP master<br />
• Number of connections, max. 16 16 32<br />
• Services<br />
- PG/OP communication Yes Yes Yes<br />
- Routing Yes Yes Yes<br />
- Global data communication No No No<br />
- S7 basic communication No No No<br />
- S7 communication Yes Yes Yes<br />
- S7 communication, as client Yes<br />
- S7 communication, as server Yes<br />
- equidistance support No No No<br />
- Activation/deactivation of No No No<br />
DP slaves<br />
- direct data exchange No No No<br />
(cross traffic)<br />
• Transmission speeds, max. 12 MBit/s 12 MBit/s 12 MBit/s<br />
• Number of DP slaves, max. 32 32 32<br />
• Address area<br />
- Inputs, max. 2 Kibyte 2Kibyte 2 Kibyte<br />
- Outputs, max. 2 Kibyte 2Kibyte 2 Kibyte<br />
• Useful data per DP slave<br />
- Inputs, max. 244 byte 244 byte 244 byte<br />
- Outputs, max. 244 byte 244 byte 244 byte<br />
DP slave<br />
• Number of connections No configuration of CPU as DP slave<br />
5<br />
Siemens ST 70 · 2009<br />
5/43