RIGGING AND HANDLING<br />

Exercise care when moving the unit. Do not remove<br />

any packaging until the unit is near the place of installation.<br />

Rig the unit by attaching chain or cable slings to<br />

the round lifting holes provided in the base rails.<br />

Spreaders, whose length exceeds the largest dimension<br />

across the unit, MUST BE USED. Refer to<br />

Figure 1.<br />

Units may also be moved or lifted with a forklift, from<br />

the side only, providing that an accessory skid is used.<br />

LENGTH OF FORKS MUST BE A MIN<strong>IM</strong>UM OF 90".<br />

Refer to the Physical Data Table 5 for unit weights and<br />

to the Figures 2 or 12 for approximate center of gravity.<br />

Before lifting a unit, make sure that all panels<br />

are in place and that its weight is distributed<br />

equally on all cables so it will lift evenly.<br />

FIGURE 2 - CENTER OF GRAVITY<br />

CLEARANCES<br />

All units require certain clearances for proper operation<br />

and service. Installer must make provisions for adequate<br />

ventilation air. Refer to Unit Dimensions<br />

Figure 10 and Minimum Clearances Table 11 for the<br />

clearances required for combustible construction, servicing,<br />

and proper unit operation.<br />

1. 6 1 /<br />

0 - 5<br />

FIGURE 1 - TYPICAL RIGGING<br />

5 2 4 - ) , - 4<br />

* ) 4<br />

+ ) 7 6 1 <br />

* - . 4 - 1. 6 1 / 7 16 <br />

) - 5 7 4 - 6 0 ) 6 16 5<br />

9 1, 6 0 15 , 15 6 4 1* 7 6 - ,<br />

- 3 7 ) ; 6 0 - + ) * - 5<br />

5 6 0 ) 6 16 9 1 1. 6<br />

- 8 - ;<br />

Do not permit overhanging structures or shrubs<br />

to obstruct outdoor air discharge outlet, combustion<br />

air inlet or vent outlets.<br />

DUCTWORK<br />

Ductwork should be designed and sized according to<br />

the methods in Manual Q of the Air Conditioning Contractors<br />

of America (ACCA).<br />

A closed return duct system shall be used. This shall<br />

not preclude use of economizers or outdoor fresh air<br />

intake. The supply and return air duct connections at<br />

the unit should be made with flexible joints to minimize<br />

noise.<br />