66394-Y<strong>IM</strong>-D-1004<br />
RIGGING AND HANDLING<br />
Exercise care when moving the unit. Do not remove<br />
any packaging until the unit is near the place of installation.<br />
Rig the unit by attaching chain or cable slings to<br />
the round lifting holes provided in the base rails.<br />
Spreaders, whose length exceeds the largest dimension<br />
across the unit, MUST BE USED. Refer to<br />
Figure 1.<br />
Units may also be moved or lifted with a forklift, from<br />
the side only, providing that an accessory skid is used.<br />
LENGTH OF FORKS MUST BE A MIN<strong>IM</strong>UM OF 90".<br />
Refer to the Physical Data Table 5 for unit weights and<br />
to the Figures 2 or 12 for approximate center of gravity.<br />
Before lifting a unit, make sure that all panels<br />
are in place and that its weight is distributed<br />
equally on all cables so it will lift evenly.<br />
FIGURE 2 - CENTER OF GRAVITY<br />
CLEARANCES<br />
All units require certain clearances for proper operation<br />
and service. Installer must make provisions for adequate<br />
ventilation air. Refer to Unit Dimensions<br />
Figure 10 and Minimum Clearances Table 11 for the<br />
clearances required for combustible construction, servicing,<br />
and proper unit operation.<br />
1. 6 1 /<br />
0 - 5<br />
FIGURE 1 - TYPICAL RIGGING<br />
5 2 4 - ) , - 4<br />
* ) 4<br />
+ ) 7 6 1 <br />
* - . 4 - 1. 6 1 / 7 16 <br />
) - 5 7 4 - 6 0 ) 6 16 5<br />
9 1, 6 0 15 , 15 6 4 1* 7 6 - ,<br />
- 3 7 ) ; 6 0 - + ) * - 5<br />
5 6 0 ) 6 16 9 1 1. 6<br />
- 8 - ;<br />
Do not permit overhanging structures or shrubs<br />
to obstruct outdoor air discharge outlet, combustion<br />
air inlet or vent outlets.<br />
DUCTWORK<br />
Ductwork should be designed and sized according to<br />
the methods in Manual Q of the Air Conditioning Contractors<br />
of America (ACCA).<br />
A closed return duct system shall be used. This shall<br />
not preclude use of economizers or outdoor fresh air<br />
intake. The supply and return air duct connections at<br />
the unit should be made with flexible joints to minimize<br />
noise.<br />
14 Unitary Products Group