66394-Y<strong>IM</strong>-D-1004<br />

TABLE 7: VOLTAGE L<strong>IM</strong>ITATIONS<br />

VOLTAGE<br />

POWER SUPPLY<br />

MIN.<br />

MAX.<br />

208/230-3-60 187 253<br />

460-3-60 414 506<br />

575-3-60 518 630<br />

TABLE 8: ELECTRICAL DATA -WITHOUT POWERED CONVENIENCE OUTLET<br />

COMPRESSORS<br />

MODEL<br />

TONNAGE VOLTAGE RLA LRA<br />

EACH EACH<br />

<strong>BQ240</strong><br />

OD FAN<br />

MOTORS<br />

FLA EACH<br />

ID<br />

BLOWER<br />

MOTOR<br />

FLA<br />

CONV<br />

OUTLET<br />

AMPS<br />

208 16.7 150 4.5 19.4 0.0<br />

230 16.7 150 4.3 21.0 0.0<br />

460 9.6 75 2.2 9.7 0.0<br />

575 6.4 62 1.7 7.8 0.0<br />

HEATER OPTION<br />

MODEL KW 2 STAGES AMPS<br />

MIN.<br />

CIRCUIT<br />

AMPACITY<br />

(AMPS)<br />

MAX.<br />

FUSE/<br />

BRKR 1<br />

SIZE<br />

(AMPS)<br />

- 0.0 - - 100.1 110<br />

E18 13.5 1 37.5 146.9 150<br />

E36 27.0 2 75.1 146.9 150<br />

E54 40.6 2 112.6 165.1 175<br />

E72 54.1 2 150.1 193.7 200<br />

- 0.0 - - 101.7 110<br />

E18 18.0 1 43.3 155.8 175<br />

E36 36.0 2 86.6 155.8 175<br />

E54 54.0 2 129.9 156.2 175<br />

E72 72.0 2 173.2 209.9 225<br />

- 0.0 - - 54.9 60<br />

E18 18.0 1 21.7 82.0 90<br />

E36 36.0 2 43.3 82.0 90<br />

E54 54.0 2 65.0 82.0 90<br />

E72 72.0 2 86.6 109.1 110<br />

- 0.0 - - 38.8 45<br />

E18 18.0 1 17.3 60.4 70<br />

E36 36.0 2 34.6 60.4 70<br />

E54 54.0 2 52.0 61.7 70<br />

E72 72.0 2 69.3 82.1 90<br />

Note 1:<br />

Note 2:<br />

Maximum HACR breaker of the same amp size is acceptable.<br />

Only 18kW of the 36 or 54kW, or only 36kW of the 72kW electric heat can be simultaneously energized with the mechanical<br />

heating. The full heater kW operates only if both compressors are locked out.<br />