14.01.2015 Views

Y-IM, BQ240 Sunline 2000 Single Package Heat Pump

Y-IM, BQ240 Sunline 2000 Single Package Heat Pump

Y-IM, BQ240 Sunline 2000 Single Package Heat Pump

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

66394-Y<strong>IM</strong>-D-1004<br />

TABLE 14: BLOWER PERFORMANCE 20 TON SUPPLY AIR BOTTOM DUCT CONNECTIONS<br />

MOTOR<br />

CFM<br />

BLOWER<br />

PULLEY<br />

SPEED,<br />

6000 7000 8000 9000 9400<br />

(TURNS<br />

(RPM)<br />

OPEN)* ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW<br />

208 VOLT AND STANDARD DRIVE<br />

870 6.0** 0.4 2.1 1.8 0.1 2.3 2.0 - - - - - - - - -<br />

900 5.0 0.8 3.2 2.7 0.5 3.5 2.9 0.2 3.8 3.2 - - - - - -<br />

930 4.0 1.1 4.1 3.4 0.9 4.5 3.8 0.6 4.9 4.1 0.1 5.1 4.3 - - -<br />

950 3.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - -<br />

980 2.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1<br />

1015 1.0 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5 0.6 8.2 6.9<br />

208 VOLT AND HIGH SPEED DRIVE<br />

950 6.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - -<br />

980 5.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1<br />

1010 4.0 1.8 5.8 4.9 1.7 6.3 5.3 1.5 6.9 5.8 1.0 7.5 6.3 0.5 7.9 6.7<br />

1020 3.5 1.9 6.1 5.1 1.8 6.5 5.5 1.6 7.1 6.0 1.1 7.8 6.6 0.6 8.3 7.0<br />

1035 3.0 2.0 6.2 5.2 1.9 6.8 5.7 1.7 7.4 6.2 1.2 8.1 6.8 0.7 8.6 7.3<br />

1050 2.5 2.1 6.4 5.4 2.0 7.0 5.9 1.8 7.6 6.4 1.3 8.3 7.0 - - -<br />

1075 2.0 2.3 6.6 5.5 2.1 7.2 6.0 1.9 7.8 6.6 1.5 8.6 7.2 - - -<br />

1100 1.0 2.4 6.7 5.6 2.2 7.3 6.1 2.1 7.9 6.7 - - - - - -<br />

230/460/575 VOLT AND STANDARD DRIVE<br />

870 6.0** 0.4 2.1 1.8 0.1 2.3 2.0 - - - - - - - - -<br />

900 5.0 0.8 3.2 2.7 0.5 3.5 2.9 0.2 3.8 3.2 - - - - - -<br />

930 4.0 1.1 4.1 3.4 0.9 4.5 3.8 0.6 4.9 4.1 0.1 5.1 4.3 - - -<br />

950 3.5 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - -<br />

980 2.5 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1<br />

1015 1.5 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5 0.6 8.2 6.9<br />

1025 1.0 2.0 6.1 5.1 1.8 6.6 5.6 1.6 7.3 6.1 1.1 7.9 6.7 0.7 8.6 7.3<br />

230/460/575 VOLT AND HIGH SPEED DRIVE<br />

950 6.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - -<br />

980 5.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1<br />

1015 4.0 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5 0.6 8.2 6.9<br />

1035 3.5 2.0 6.2 5.2 1.9 6.8 5.7 1.7 7.4 6.2 1.2 8.1 6.8 0.7 8.6 7.3<br />

1050 3.0 2.1 6.4 5.4 2.0 7.0 5.9 1.8 7.6 6.4 1.3 8.3 7.0 - - -<br />

1080 2.0 2.3 6.6 5.5 2.1 7.2 6.0 1.9 7.8 6.6 1.5 8.6 7.2 - - -<br />

1100 1.5 2.4 6.7 5.6 2.2 7.3 6.1 2.1 7.9 6.7 - - - - - -<br />

1120 1.0 2.5 6.8 5.7 2.3 7.4 6.2 2.2 8.1 6.8 - - - - - -<br />

NOTES:<br />

1. Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.<br />

2. Refer to Table 15 for additional static resistances.<br />

ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the<br />

total static pressure of the blower.<br />

* Do NOT close the pulley below 1 turn open.<br />

** Factory setting.<br />

30 Unitary Products Group

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!