66394-Y<strong>IM</strong>-D-1004<br />
BLOWER<br />
ACCESS<br />
BLOWER MOTOR<br />
ACCESS<br />
BLOWER<br />
COMPARTMENT<br />
ACCESS<br />
(Auxiliary)<br />
FIELD-SUPPLIED<br />
DISCONNECT SWITCH<br />
LOCATION<br />
ECONOMIZER / MOTORIZED DAMPER,<br />
FIXED OUTDOOR INTAKE AIR AND<br />
POWER EXHAUST RAIN HOODS<br />
(See detail "Y")<br />
COMPRESSOR<br />
ACCESS<br />
(See detail "X")<br />
48-1/4" (20 TON)<br />
OPTIONAL COIL<br />
GUARD KIT<br />
DOT PLUG<br />
(For pressure<br />
Drop Reading)<br />
FRONT<br />
VIEW<br />
136-1/4" (20 TON)<br />
ELECTRIC HEAT<br />
ACCESS<br />
CONTROL BOX<br />
ACCESS<br />
35"<br />
21"<br />
5"<br />
9-3/4"<br />
5-7/8"<br />
11-1/2"<br />
92"<br />
BOTTOM SUPPLY<br />
AND RETURN<br />
AIR OPENINGS<br />
(See Note)<br />
CONDENSER<br />
COILS<br />
(A)<br />
CONTROL WIRING<br />
ENTRY<br />
(B)<br />
POWER WIRING<br />
ENTRY<br />
All dimensions are in inches. They are<br />
subject to change without notice. Certified<br />
dimensions will be provided upon<br />
request.<br />
RETURN AIR<br />
35-1/4" (20 TON)<br />
RETURN<br />
AIR<br />
33"<br />
SUPPLY<br />
AIR<br />
2-3/4" 21-1/2"<br />
3-3/4"<br />
SUPPLY AIR<br />
OUTDOOR AIR<br />
OUTDOOR AIR<br />
(Economizer)<br />
UNIT BASE WITH RAILS<br />
Shown separately to illustrate<br />
Bottom Duct openings andPower<br />
Connection locations<br />
NOTE:<br />
For curb mountedunits, refer to the curb hanger<br />
dimensions of the curb for the proper size of the<br />
supply andreturn air duct connections.<br />
9-1/4"<br />
12-1/2"<br />
8-1/8"<br />
9-3/4"<br />
(B)<br />
POWER WIRING<br />
ENTRY<br />
(A)<br />
CONTROL WIRING<br />
ENTRY<br />
FIGURE 10 - UNIT D<strong>IM</strong>ENSIONS - 20 TON<br />
TABLE 11: MIN<strong>IM</strong>UM CLEARANCES<br />
LOCATION<br />
CLEARANCE<br />
Front 36”<br />
Back<br />
24” (Less Economizer)<br />
49” (With Economizer<br />
Left Side (Filter Access)<br />
24” (Less Economizer)<br />
36” (With Economizer)<br />
Right Side (Cond. Coil) 36”<br />
Below Unit 1<br />
0”<br />
72” With 36” Maximum<br />
Above Unit 2<br />
Horizontal Overhang (For<br />
Condenser Air Discharge)<br />
TABLE 12: UTILITIES ENTRY DATA<br />
HOLE OPENING SIZE (DIA.) USED FOR<br />
A<br />
B<br />
1-1/8” KO<br />
Control Wiring<br />
Front<br />
3/4” NPS (Fem.) Bottom<br />
3-5/8” KO<br />
Front<br />
Power Wiring<br />
3” NPS (Fem.) Bottom<br />
NOTE: All entry holes should be field sealed to prevent rain<br />
water entry into building.<br />
1. Units (applicable in U.S.A. only) may be installed on<br />
combustible floors made from wood or class A, B or C<br />
roof covering material.<br />
2. Units must be installed outdoors. Overhanging structures<br />
or shrubs should not obstruct outdoor air discharge<br />
outlet.<br />
NOTE: Units and ductwork are approved for zero clearance to<br />
combustible materials when equipped with electric heaters.<br />