13<br />
3.4.2 System overview model “flow C”<br />
Volume controlling valves<br />
(adjustable manually)<br />
Humidification boxes<br />
Supply valve<br />
Water tub<br />
Water connection unit (accessory)<br />
Water filter<br />
Control unit RC<br />
Output:<br />
Supply valve<br />
Open drain<br />
Siphon (building side)<br />
Pressure reducing valve<br />
L1 N S S<br />
Drain funnel (building side)<br />
Shut-off valve<br />
Humidistat 230V/2A<br />
%rH<br />
Water supply<br />
2...10 bar<br />
Input:<br />
Potential free contact 230 V<br />
PE L1 N<br />
Functional description<br />
The “flow C” model provides On/Off control by means of the RC control unit and an external On/Off<br />
humidistat. In case of a humidification/cooling request the supply valve opens and the water flows<br />
via the pressure reducing valve (accessory), the water filter (accessory) and the manually adjustable<br />
volume controlling valves to the distribution pipes above the humidification boxes.<br />
The distribution pipes evenly supply the water to the entire surface of the humidification boxes where<br />
it flows down and humidifies the air flowing through the humidification boxes. The excess water not<br />
used for humidification flows to the water tub and then directly to the drain.