13<br />

3.4.2 System overview model “flow C”<br />

Volume controlling valves<br />

(adjustable manually)<br />

Humidification boxes<br />

Supply valve<br />

Water tub<br />

Water connection unit (accessory)<br />

Water filter<br />

Control unit RC<br />

Output:<br />

Supply valve<br />

Open drain<br />

Siphon (building side)<br />

Pressure reducing valve<br />

L1 N S S<br />

Drain funnel (building side)<br />

Shut-off valve<br />

Humidistat 230V/2A<br />

%rH<br />

Water supply<br />

2...10 bar<br />

Input:<br />

Potential free contact 230 V<br />

PE L1 N<br />

Functional description<br />

The “flow C” model provides On/Off control by means of the RC control unit and an external On/Off<br />

humidistat. In case of a humidification/cooling request the supply valve opens and the water flows<br />

via the pressure reducing valve (accessory), the water filter (accessory) and the manually adjustable<br />

volume controlling valves to the distribution pipes above the humidification boxes.<br />

The distribution pipes evenly supply the water to the entire surface of the humidification boxes where<br />

it flows down and humidifies the air flowing through the humidification boxes. The excess water not<br />

used for humidification flows to the water tub and then directly to the drain.