– We recommend to install air filter (quality standard F7 (EU7) or better) before the humidification<br />
unit. The operation without air filter or with a filter of lower quality is possible, this can however,<br />
depending on the air quality, lead to an increased contamination of the humidifier boxes and thus<br />
to a reduction of the performance/lifetime.<br />
– In case of low ambient temperature the duct must be insulated to prevent the moist air from<br />
condensing inside the duct.<br />
– If the system is equipped with a heater, make sure it is at least 0.5 m away from the humidification<br />
unit.<br />
– If silencers are mounted in the airconditioning units make sure to locate the humidification unit<br />
at a minimum distance of 3 m before or after the silencers.<br />
– In order to avoid drops seeping over the humidification boxes, an even air flow over the full cross<br />
section of the humidification unit must be guaranteed. If necessary, rectifiers or perforated plates<br />
must be installed on the building side before the humidifier.<br />
If the air velocity above the humidification boxes exceeds 3.8 m/s, mist eliminator must be installed.<br />
– The effective height of the siphon in the drain line depends on the duct pressure. Correct dimensioning<br />
of the siphon is the customer’s responsibility.