Product description <strong>com</strong>munication<br />
Dok.nr.:UK\PD\ZU\PowCom<br />
Rev.: F<br />
program - PowCom Page 16 of 27<br />
Prepared: Arild Sagebø Date: 08.03.2000<br />
Number of batteries<br />
Sets the number of branches on the battery that are equipped with symmetry<br />
me<strong>as</strong>uring.<br />
Boost time<br />
Sets the duration of boost charging.<br />
Boost interval<br />
Sets the number of weeks between each boost.<br />
Boost factor<br />
Used to set the duration of boost after mains failure. See T1 LIMIT and T2<br />
LIMIT.<br />
T1 limit<br />
When the voltage reaches below this limit, the system starts counting time.<br />
When the voltage reaches over this limit again, the counting stops. The counted<br />
time is used in a function with the boost factor when the voltage reaches over<br />
T2 LIMIT.<br />
T2 limit<br />
When the system reaches over this limit the boost will start. The duration will<br />
be the time from T1 LIMIT multiplied with the boost factor.<br />
Over voltage shutdown<br />
If the voltage reaches over this limit, the rectifier which delivers the highest<br />
current will be switched off<br />
High load<br />
Entered in percent of the maximum power from the system. If the load current<br />
get higher this limit, the system will give alarm to signal that there may not be<br />
enough capacity to charge the battery.<br />
Test time<br />
Sets the time of day (0-23) when automatic test should start. E.g. 4 - the test<br />
starts at 04.00.<br />
Automatic test<br />
Sets how many times each year automatic test shall be performed.<br />
Battery type<br />
Sets the type of battery which connected. Indicates how many blocks each<br />
branch is divided into for symmetry me<strong>as</strong>urements