17. Set system status (only PCU 30.00)<br />

17.1. Control module active<br />

Controls if the control module is allowed to regulate the output voltage of the<br />

rectifier modules. Should be active during normal operation. Will automatically<br />

be set "not active" at e.g. change of EPROM. The procedure is to adjust all<br />

parameters for voltage, alarms, levels etc. and then activate the control module.<br />

17.2. Automatic boost charging<br />

Sets the automatic boost charging (boost) active. Must only be activated if the<br />

batteries shall be boost charged.<br />

17.3. Temperature <strong>com</strong>pensating<br />

Activates the temperature <strong>com</strong>pensation. The charging voltage will be adjusted<br />

continuously according to the <strong>com</strong>pensation factor.<br />

17.4. Compensation factor<br />

Is the factor with which the charging voltage will be changed when the<br />

temperature <strong>com</strong>pensation is active. The adjusted charging voltage refers to 20<br />

degrees C. If the temperature rises with 10 degrees, the voltage will be reduced<br />

according to the adjusted <strong>com</strong>pensation factor. If the temperature goes down<br />

the voltage will be adjusted correspondingly. The adjustment is done<br />

continuously, which means that if the temperature is changed with 1 degree, the<br />

voltage will be changed with 1/10 of the <strong>com</strong>pensation factor.<br />

17.5. Modules<br />

Set the modules which are installed in the system. 1-31 are rectifier modules<br />

and 33 is the alarm unit (PAU). Tick off the installed rectifier modules. PAU<br />

(33) shall always be activated.<br />

17.6. Automatic test (only PCU with lower software versions than 3.20)<br />

States if an automatic test shall be executed once a year. PCU 30 with V3.20 or<br />

higher have several options for automatic test.