17. Set system status (only PCU 30.00)<br />
17.1. Control module active<br />
Controls if the control module is allowed to regulate the output voltage of the<br />
rectifier modules. Should be active during normal operation. Will automatically<br />
be set "not active" at e.g. change of EPROM. The procedure is to adjust all<br />
parameters for voltage, alarms, levels etc. and then activate the control module.<br />
17.2. Automatic boost charging<br />
Sets the automatic boost charging (boost) active. Must only be activated if the<br />
batteries shall be boost charged.<br />
17.3. Temperature <strong>com</strong>pensating<br />
Activates the temperature <strong>com</strong>pensation. The charging voltage will be adjusted<br />
continuously according to the <strong>com</strong>pensation factor.<br />
17.4. Compensation factor<br />
Is the factor with which the charging voltage will be changed when the<br />
temperature <strong>com</strong>pensation is active. The adjusted charging voltage refers to 20<br />
degrees C. If the temperature rises with 10 degrees, the voltage will be reduced<br />
according to the adjusted <strong>com</strong>pensation factor. If the temperature goes down<br />
the voltage will be adjusted correspondingly. The adjustment is done<br />
continuously, which means that if the temperature is changed with 1 degree, the<br />
voltage will be changed with 1/10 of the <strong>com</strong>pensation factor.<br />
17.5. Modules<br />
Set the modules which are installed in the system. 1-31 are rectifier modules<br />
and 33 is the alarm unit (PAU). Tick off the installed rectifier modules. PAU<br />
(33) shall always be activated.<br />
17.6. Automatic test (only PCU with lower software versions than 3.20)<br />
States if an automatic test shall be executed once a year. PCU 30 with V3.20 or<br />
higher have several options for automatic test.