AL 2000 User Guide<br />

Page 3 - 1<br />

06/05/00<br />

3. HARDWARE CONFIGURATION<br />

3.1 Selection of Mounting Rack<br />

The number of the I/O modules and CPU type must be considered when selecting the<br />

mounting rack. If the process to be controlled is spread over a large area, considerable<br />

savings can be achieved by using the AL2000 to implement a distributed control system<br />

utilising several remote units. In this case only the central unit requires PLC programming,<br />

the remote units operate as Modbus RTU I/O units only.<br />

Five different mounting racks are available:<br />

1. MR3-mini for up to 3 I/O modules (CPU2000SCP)<br />

2. MR3 for up to 3 I/O modules<br />

3. MR5 for up to 5 I/O modules<br />

4. MR11 for up to 11 I/O modules<br />

5. MR16 for up to 16 I/O modules<br />

PWR CPU 0 1 2<br />

POW<br />

CPU 0 1 2 3 4<br />

PCON<br />

POW<br />

POW<br />

CPU 0 1 2 3 4 5 6 7 8 9 10<br />

CPU 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15<br />

PCON<br />

PCON<br />

3.2 Selection of Power Input Module(s)<br />

The AL2000 power supply is made up of two separate parts, the power connecting module<br />

and the power supply module. All mounting racks except the MR3 and MR3-mini<br />

must be fitted with both of these units. A different, single-unit power supply is included<br />

with the MR3 and the MR3-mini requires no power supply (the CPU2000SCP has its own<br />

power supply).<br />

There are two types of power connecting module available, the PCON230 and the<br />

PCON24. These must be used in conjunction with the POWAC and POWDC power supply<br />

modules respectively:<br />

PCON230 and POWAC: Input voltage 230VAC<br />

Suitable for MR5, MR11, MR16<br />

PCON24 and POWDC: Input voltage 24VAC/DC<br />

Suitable for MR5<br />

PWR3: Input voltage 230VAC or 24VAC/DC<br />

Suitable for MR3 only<br />