AL 2000 User Guide<br />
Page 5 - 23<br />
11/09/2000<br />
5.3.3 AIC8 Analog Input Module<br />
The AIC8 is an analog input module with 8 x 12-<br />
bit differential or 16 x 12-bit non-differential analog<br />
inputs isolated as a group. The maximum<br />
common mode voltage for the AIC8 is 40V. The<br />
current consumption of AIC8 is 250 mA.<br />
The ranges of the AIC8 are as follows:<br />
Inputs:<br />
Voltage<br />
0-480mV (0-4000) 8.3 bits/mV<br />
0-5V (0-4000) 800 bits/V<br />
0-10V (0-4000) 400 bits/V<br />
±10V (0-4000) 200 bits/V<br />
Current<br />
0(4)-20mA (0-4000) 200 bits/mA<br />
Pt100 385<br />
(-50 to 150ºC) (0-4000) 20 bits/ºC<br />
(-200 to 730ºC) (0-3720) 4 bits/ºC<br />
KTY10<br />
(-50 to 150ºC) (0-2000) 10 bits/ºC<br />
Pt100 391<br />
(-200 to 730ºC) (0-3720) 4 bits/ºC<br />
Cu50<br />
(-200 to 200ºC) (100-900) 2 bits/ºC<br />
A constant measuring current of 1.4mA is provided<br />
for each input.<br />
The following LED indicators are located on the<br />
front edge of the module:<br />
ACT (green) Module is in operation<br />
ERR (red) The operating system has discovered a<br />
fault<br />
in the module<br />
0-7 (red) Status of analog inputs AI0-AI6<br />
STEADY LIGHT: input not scaled<br />
FLASHING LIGHT: input at upper/lower<br />
limit or not connected<br />
NO LIGHT: input in use and OK<br />
<strong>FF</strong>-<strong>Automation</strong> Oy