Man Al2000_eng.pdf - FF-Automation
Man Al2000_eng.pdf - FF-Automation
Man Al2000_eng.pdf - FF-Automation
- No tags were found...
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
AL 2000 User Guide<br />
Page 4 - 3<br />
06/05/00<br />
4.1.2 Addresses of Inputs and Outputs<br />
All I/O points have addresses, these are used by MODBUS. The address assignment can<br />
be seen on the ALPro configuration screen's I/O map. I/O addresses are assigned in<br />
blocks of 16, therefore there will be unused addresses if an I/O module requires less then<br />
16 addresses. For an AIO74 module the used/unused addresses are:<br />
AIO74 Inputs 0 1 2 3 4 5 6 - 8 9 10 11 12 13 14 -<br />
AIO74 Outputs 0 1 2 3 - - - - - - - - - - - -<br />
Unused addresses are represented by the '-' symbol<br />
4.1.3 Serial Port Configuration<br />
The AL2000 has 3 serial interfaces of which all can be configured to function as MODBUS<br />
Slave and MODBUS Master (independently of one another). These are:<br />
SER 1, SER 2<br />
SER 3<br />
RS-232<br />
RS-485<br />
The serial ports must be configured for the required baud rate and MODBUS master/<br />
slave mode. This is done by initialising the following register outputs:<br />
MODBUS modes SER 1, SER 2, SER 3 MODBUS Slave/MODBUS Master<br />
Baud Rates SER 1, SER 2, SER 3 0,3/1,2/2,4/4,8/9,6/19,2 kbit/s<br />
28,8/38,4/57,6/115,2 kbit/s<br />
Maximum cable l<strong>eng</strong>th for RS-232 is 15m for 9600 bit/s<br />
Maximum cable l<strong>eng</strong>th for RS-485 is 1200m for 9600 bit/s<br />
4.2 Setting Up A MODBUS Master<br />
A MODBUS master can be set up on SER1 and/or SER2 and/or SER3 by following the<br />
steps below.<br />
Example: Set The Serial Port 2 to Modbus MASTER, baud rate 9600,N,8,1<br />
STR R C 5<br />
EQ R O 215 ; set SER2 to MASTER mode<br />
STR R C 4<br />
EQ R O 229 ; set SER2 baud rate to 9600<br />
STR R C 0<br />
EQ R O 219 ; set SER 2 data configuration to 8,N,1<br />
See chapter 9.3 Register Output Configuration for available baud rates, communication<br />
modes and data configuration modes.<br />
<strong>FF</strong>-<strong>Automation</strong> Oy