Wiring Connections<br />

Wiring Overview<br />

The following summarizes the connections required. Refer to the Wiring Connections paragraph and the Summary of<br />

Connections diagram on the inside back cover when making connections.<br />

HARDWIRE ZONE<br />

Supports 1 EOLR supervised zone using either closed<br />

circuit or open circuit sensors.<br />

LONG RANGE RADIO<br />

Compatible with the ALARMNET 7845C and 7720<br />

Devices.<br />

TWO-WAY VOICE<br />

The <strong>LYNXR</strong>-EN supports the two-way<br />

voice feature/<strong>Alarm</strong> Audio Verification.<br />

The <strong>LYNXR</strong> and <strong>LYNXR</strong>24 require the<br />

installation of the LYNXAVM.<br />

POWERLINE CARRIER DEVICES<br />

Supports up to 8 Powerline Carrier<br />

Devices for turning on/off lights and<br />

appliances. Requires the use of an<br />

<strong>ADEMCO</strong> 1332X10 transformer.<br />

PHONE LINES<br />

Use either the plug-in jacks or<br />

the screw terminals.<br />

MXXXX<br />

K5108<br />

AC TRANSFORMER<br />

Use the supplied<br />

<strong>ADEMCO</strong> 1332X10<br />

9VAC, 15VA Plug-in<br />

Transformer (1332CN in<br />

Canada).<br />

01009-005-V0<br />

EARTH GROUND<br />

See Earth Ground paragraph.<br />

LOCAL SOUNDER DISABLE JUMPER<br />

Remove the shorting jumper (shunt) to disable local<br />

sounder, leaving only the external sounder active.<br />

UL NOTE: Do not remove the shorting jumper (the shunt)<br />

for UL installations.<br />

SOUNDERS<br />

The system includes a built-in sounder in the master keypad. If<br />

desired, an external bell or piezo sounder can be connected.<br />

Bell: Use a 6-14V bell with maximum current drain of 120mA.<br />

Piezo: Use a 6-14V piezo sounder with maximum current drain of<br />

30mA.<br />

This control complies with NFPA requirements for temporal pulse<br />

sounding of fire notification appliances.<br />

Temporal pulse sounding for a fire alarm consists of the following:<br />

3 pulses – pause – 3 pulses – pause – 3 pulses. . .<br />

Wiring Connections<br />

1. Make Earth Ground Connection - The designated earth ground terminal (1) must be terminated in a good earth ground<br />

for the lightning transient protective devices in this product to be effective. The following are examples of good earth<br />

grounds available at most installations:<br />

Metal Cold Water Pipe - Secure a non-corrosive metal strap (copper is recommended) to the pipe that is electrically<br />

connected and secured to which the ground lead.<br />

AC Power Outlet Ground - Available from 3-prong, 120VAC power outlets only. To test the integrity of the ground<br />

terminal, use a three-wire circuit tester with neon lamp indicators, such as the UL Listed Ideal Model 61–035, or<br />

equivalent, available at most electrical supply stores.<br />

a. Connect terminal 1 to a good earth ground.<br />