5 Project planning information<br />
5.1 Installation<br />
Installation position: any.<br />
Gas and air connection: can be rotated in 90° steps.<br />
Install and insulate the burner in order to avoid any overheating<br />
of the components during operation. Where applicable,<br />
purging air must be used to prevent ingress of aggressive<br />
gases and thermal overload of components.<br />
Purging air bore holes in the furnace flange area ensure cooling<br />
and stability in the case of combustion in small combustion<br />
chambers (for example radiant tubes).<br />
5.2 Recommended ignition transformer<br />
≥ 7.5 kV, ≥ 12 mA, e.g. TZI 7,5-12/100 or TGI 7,5-12/100.<br />
5.3 Nozzle-mixing burners<br />
Non-return gas valves are not required, since the burners are<br />
of the nozzle-mixing type.<br />
5.4 Flame control<br />
Flame control is performed using an ionisation electrode or<br />
optionally using a UV sensor.<br />
5.5 Hot air compensation<br />
In order to maintain the total connection rating constant in<br />
hot-air operating mode:<br />
1. Gas connection rating and gas pressure are reduced<br />
Total connection rating [%]<br />
100<br />
96<br />
90<br />
85<br />
80<br />
75<br />
0 50 100 150 200 250 300 350 400 450<br />
Combustion air temperature [°C]<br />
2. Air pressure is increased<br />
air pressure [%]<br />
200<br />
180<br />
160<br />
140<br />
120<br />
Gas connection rating<br />
Gas pressure<br />
100<br />
0 50 100 150 200 250 300 350 400 450<br />
Combustion air temperature [°C]<br />
<strong>BIO</strong>, <strong>BIO</strong>A, <strong>ZIO</strong> · Edition 12.08