21.03.2015 Views

BIO, BIOA, ZIO

BIO, BIOA, ZIO

BIO, BIOA, ZIO

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Project planning information<br />

22<br />

5.8 Gas line connection<br />

To ensure accurate measurements of the pressure differential<br />

on the integrated gas measuring orifice for burners <strong>BIO</strong> as<br />

from construction stage E, the following applies for the design<br />

of the gas connection:<br />

– Ensure undisturbed flow to the gas connection on the burner<br />

for a distance of ≥ 5 DN.<br />

– Use a bellows unit with the same nominal dimensions as<br />

the gas connection on the burner.<br />

– Use a pipe bend up to an angle of 90° with the same nominal<br />

dimensions as the gas connection on the burner.<br />

– Only use reducing nipples with an external thread at both<br />

ends in order to reduce the nominal diameter on the burner<br />

(e.g. from 1” to ¾”).<br />

To ensure optimum flow, to avoid incorrect measurements and<br />

to enable burner operation with excess gas, we recommend<br />

the following:<br />

– Do not screw the manual valve directly into the burner.<br />

5.9 Air line connection<br />

Ensure there is a bellows unit and an air adjusting cock upstream<br />

of the burner. It is recommended to install a measuring<br />

orifice FLS to determine the air flow rate.<br />

<strong>BIO</strong>, <strong>BIO</strong>A, <strong>ZIO</strong> · Edition 12.08

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!