4<br />
Technical data<br />
General data and operating conditions<br />
4 Technical data<br />
4.1 General data and operating conditions<br />
General data<br />
Conformity and approval<br />
Conformity<br />
CE 1) 2006/95/EC Low−Voltage Directive<br />
2009/125/EC ErP Directive<br />
Approvals<br />
<br />
File No. E210321 UL/CSA<br />
CCC<br />
1) Does not apply to all products, 11<br />
Protection of persons and equipment<br />
Degree of protection IEC/EN 60034−5 See nameplate<br />
Degrees of protection only apply to horizontal installation<br />
All unused plug−in connections must be sealed with protective<br />
caps or dummy connectors.<br />
Thermal class<br />
F (155 °C)<br />
IEC/EN 60034−1<br />
Exceedance of the temperature limit weakens or destroys the<br />
insulation<br />
Permissible voltage<br />
According to limiting curve A of the pulse voltage from<br />
IEC / TS 60034−25 (image 14)<br />
EMC<br />
Noise emission IEC/EN 61800−3 Depending on the controller, see documentation for the<br />
Noise immunity<br />
controller.<br />
<strong>Operating</strong> conditions<br />
Ambient conditions<br />
Climatic<br />
Transport IEC/EN 60721−3−2 2K3 (−20 °C ... +70 °C)<br />
Storage IEC/EN 60721−3−1 1K3 (−20 °C ... +60 °C) < 3 months<br />
1K3 (−20 °C ... +40 °C) > 3 months<br />
Operation IEC/EN 60721−3−3 3K3 (−20 °C ... +40 °C) Without brake<br />
3K3 (−10 °C ... +40 °C) With brake<br />
3K3 (−15 °C ... +40 °C) With power reduction<br />
> +40 °C With power reduction see,<br />
catalogue<br />
Site altitude<br />
< 1000 m amsl − without power reduction<br />
> 1000 m amsl < 4000m amsl with power reduction, see<br />
catalogue<br />
Humidity<br />
Average relative humidity 85 %, without condensation<br />
Electrical<br />
Motor connection dependent on the controller ( 33)<br />
Length of motor cable<br />
Length of cable for speed feedback<br />
Mechanical<br />
IEC/EN60721−3−3<br />
inverter instructions<br />
3M6<br />
24 <br />
BA 33.0005−EN 2.0