<strong>Steam</strong> <strong>Generator</strong> & Fluid Heater<br />
<strong>Installation</strong> <strong>Manual</strong><br />
NOTE 1: Barometric dampers are recommended on all installations with stack heights over 20 feet (6 meters)<br />
and on any low NOx units.<br />
NOTE 2: A removable, 4 feet (1.2 meters) minimum, stack section is recommended to facilitate steam<br />
generator/fluid heater maintenance and repair.<br />
NOTE 3: A backdraft damper must be installed in the exhaust stack for installations in cold weather climates.<br />
All backdraft dampers must be air-tight and proof-of-position switches.<br />
NOTE 4: Oil-fired units require a 2W x 3H feet (0.6W x 0.9H meter) access portal in the stack for inspection and<br />
water washing. A floor drain is required at the bottom of the generator under or close to the burner<br />
opening.<br />
Figure 2-2 Standard exhaust stack layout for natural gas and light-oil installations only. Not recommended for<br />
heavy-oil machines.<br />
Sect02_Genrl-xx4_s.fm 2-8 04/21/2015