NOTE 1: Barometric dampers are recommended on all installations with stack heights over 20 feet (6 meters)<br />
and on low NOx units.<br />
NOTE 2: A removable, 4 feet (1.2 meters) minimum, stack section is recommended to facilitate steam<br />
generator/fluid heater maintenance and repair.<br />
NOTE 3: An air-tight backdraft (shut off) damper must be installed in the exhaust stack for installations in cold<br />
weather climates.<br />
NOTE 4: It is recommended that all stack sections be manufactured from 316L stainless steel<br />
Figure 2-6 OPTION 2: Recommended exhaust stack installation for steam generator/fluid heaters with <strong>Clayton</strong><br />
condensing economizer.<br />
Sect02_Genrl-xx4_s.fm 2-12 04/21/2015