<strong>vacon</strong> • 25Power cabling3 = Symmetrical power cable equipped with compact low-impedance shield and intendedfor the specific mains voltage. [MCCMK, EMCMK or similar recommended; Recommendedcable transfer impedance (1...30MHz) max. <strong>100</strong>mohm/m]. See Figure 18.*360º earthing of the shield with cable glands in motor end needed for EMC level C2.4 = Screened cable equipped with compact low-impedance shield (JAMAK, SAB/ÖZCuY-Oor similar).PE conductorand shieldPE conductorsShieldFigure 18.NOTE: The EMC requirements are fulfilled at factory defaults of switching frequencies (allframes).NOTE: If safety switch is connected the EMC protection shall be continuous over the whole cable<strong>installation</strong>.4Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205