Power cabling <strong>vacon</strong> • 264.1 UL standards on cablingTo meet the UL (Underwriters Laboratories) regulations, use a UL-approved copper cable witha minimum heat-resistance of +60/75°C. Use Class 1 wire only.The units are suitable for use on a circuit capable of delivering not more than <strong>100</strong>,000 rms symmetricalamperes, 600V maximum.4.1.1 Cable dimensioning and selectionTable 15 shows the minimum dimensions of the Cu/Al-cables and the corresponding fuse sizes.Recommended fuse types are gG/gL.These instructions apply only to cases with one motor and one cable connection from the ACdrive to the motor. In any other case, ask the factory for more information.24-hour support +358 (0)201 212 575 • Email: <strong>vacon</strong>@<strong>vacon</strong>.com4